Economiser Surface Area (LMTD Method)

Economiser duty from the feedwater temperature rise, the flue gas outlet temperature and the counterflow surface area from U and LMTD, with the approach (IAPWS-IF97).

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationPulp and paperFood, dairy and textileIAPWS-IF97 (water and steam)BoilerEconomiser and air preheater

Inputs

Examples: 14 kg/s water at 70 bar(a), 150 to 230 °C; gas 37 kg/s at 380 °C; U 503 kg/s at 18 bar(a), 105 to 160 °C; gas 6 kg/s at 300 °C; U 40HRSG: 20 kg/s at 90 bar(a), 110 to 280 °C; gas 120 kg/s at 330 °C; U 45

Referred to the surface the area is quoted on (usually the gas-side surface) and including fouling; a clean-tube U undersizes economisers on coal.

Results

Supercritical pressure: there is no saturation temperature, so the approach is not defined.

Surface area needed158.67m²
Economiser duty704.43kW
Gas temperature leaving191.29°C
Log mean temperature difference (counterflow)110.99K
Approach to saturation at the outlet47.120K

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 14 kg/s water at 70 bar(a), 150 to 230 °C; gas 37 kg/s at 380 °C; U 50. The inputs, in the units selected above:

InputValue
Feedwater flow50,400 kg/h
Feedwater pressure (absolute)70.000 bar
Feedwater in150.00 °C
Feedwater out230.00 °C
Flue gas flow133,200 kg/h
Mean specific heat of the flue gas1.0900 kJ/(kg·K)
Gas temperature entering380.00 °C
Overall heat transfer coefficient (on the area A, with fouling)50.000 W/(m²·K)

Applying the formula below gives:

ResultValue
Surface area needed780.84 m²
Economiser duty4,966.5 kW
Gas temperature leaving256.85 °C
Log mean temperature difference (counterflow)127.21 K
Approach to saturation at the outlet55.830 K

Open this example in the calculator and change any input.

Formula

\(\dot Q = \dot m_w\,(h_{w,2} - h_{w,1}) \qquad T_{g,2} = T_{g,1} - \frac{\dot Q}{\dot m_g c_{p,g}} \qquad LMTD = \frac{(T_{g,1} - T_{w,2}) - (T_{g,2} - T_{w,1})}{\ln\frac{T_{g,1} - T_{w,2}}{T_{g,2} - T_{w,1}}} \qquad A = \frac{\dot Q}{U\,LMTD}\)

Variables

Symbol Meaning SI unit
\(\dot m_w\) feedwater flow kg/s
\(p_w\) feedwater pressure Pa
\(T_{w,1}\) water in K
\(T_{w,2}\) water out K
\(\dot m_g\) gas flow kg/s
\(c_{p,g}\) gas specific heat J/(kg·K)
\(T_{g,1}\) gas in K
\(U\) overall coefficient W/(m²·K)
\(A\) surface area m²
\(\dot Q\) duty W
\(T_{g,2}\) gas out K
\(LMTD\) log mean temperature difference K
\(\Delta T_{sat}\) approach to saturation K
\(h_{w,1}, h_{w,2}\) water enthalpies (IF97) J/kg

Method and standards

Water duty from FireCAD's IAPWS-IF97 enthalpies, gas heat balance with mean specific heat, counterflow LMTD.

Where it is used

  • Sizing economisers for new boilers and retrofits.
  • HRSG economiser sections.
  • Checking an existing economiser for higher duty.

Common mistakes

  • Using a clean U for coal-fired service.
  • Designing too close to saturation.
  • Ignoring the cold-end metal temperature against acid dew point.

Assumptions and limits

  • Counterflow, constant U and gas specific heat; water single-phase.
  • U is referred to the area quoted (usually the gas-side surface) and must include fouling.
  • Warnings appear when the water leaves within 20 K of saturation or the cold-end difference is under 10 K.
  • At or above the critical pressure (22.064 MPa) there is no saturation temperature, so the approach is not shown.

References

  • LMTD method
  • IAPWS R7-97 IF97

Questions and answers

How big an economiser do I need?

14 kg/s of feedwater at 70 bar(a) heated from 150 to 230 °C takes 4.97 MW; gas at 380 °C (37 kg/s) leaves at 257 °C. The counterflow LMTD is 127 K, so U = 50 W/(m²·K) needs 781 m².

What approach should I keep?

The water should leave well below saturation (here 56 K) so it does not steam at part load; steaming economisers are a different design.

Bare or finned tubes?

Finned tubes put more area per metre for clean gas; for dusty coal gas bare tubes resist fouling and erosion.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.