Worked example
Example: Coal boiler: gas 37 kg/s 350 to 180 °C, water 14.2 kg/s at 70 bar(a) from 150 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Flue gas flow | 133,200 kg/h |
| Mean specific heat of the flue gas | 1.0800 kJ/(kg·K) |
| Gas temperature in | 350.00 °C |
| Gas temperature out | 180.00 °C |
| Feedwater flow | 51,120 kg/h |
| Feedwater pressure (absolute) | 70.000 bar |
| Feedwater temperature in | 150.00 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Feedwater temperature out | 255.98 °C |
| Economiser duty | 6,793.2 kW |
| Approach to saturation (steaming margin) | 29.851 K |
| Feedwater temperature rise | 105.98 K |
| Feedwater enthalpy out | 1,114.7 kJ/kg |
Open this example in the calculator and change any input.
Formula
\(\dot Q = \dot m_g\,c_{p,g}\,(T_{g,1} - T_{g,2}) \qquad h_{w,2} = h_{w,1} + \frac{\dot Q}{\dot m_w} \qquad T_{w,2} = T(p_w, h_{w,2})\)
\(\Delta T_w = T_{w,2} - T_{w,1} \qquad \Delta T_{sat} = T_{sat}(p_w) - T_{w,2}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_g\) | flue gas flow | kg/s |
| \(c_{p,g}\) | mean specific heat of flue gas | J/(kg·K) |
| \(T_{g,1}\) | gas temperature in | K |
| \(T_{g,2}\) | gas temperature out | K |
| \(\dot m_w\) | feedwater flow | kg/s |
| \(p_w\) | feedwater pressure, absolute | Pa |
| \(T_{w,1}\) | feedwater temperature in | K |
| \(T_{w,2}\) | feedwater temperature out | K |
| \(\dot Q\) | economiser duty | W |
| \(\Delta T_{sat}\) | approach to saturation | K |
| \(\Delta T_w\) | feedwater temperature rise | K |
| \(h_{w,1}\) | feedwater enthalpy in | J/kg |
| \(h_{w,2}\) | feedwater enthalpy out | J/kg |
| \(T_{sat}\) | saturation temperature at feedwater pressure | K |
Method and standards
A first-law balance across the economiser: gas-side duty from flow, mean specific heat and temperature drop; water-side outlet enthalpy and temperature by FireCAD's IAPWS-IF97 (backward equation T(p,h)). Heat loss from the economiser casing is neglected.
Where it is used
- Checking an economiser's performance from plant readings.
- Sizing a new or added economiser at the proposal stage, before the surface area is found with the LMTD.
- Checking that the water stays below saturation at part load.
- Heat recovery steam generators and waste heat boilers, for the economiser section.
Common mistakes
- Using the specific heat at one temperature instead of the mean over the range.
- Ignoring air leakage: a measured gas outlet temperature with leakage air mixed in is too low.
- Forgetting the feedwater recirculation or bypass, so the water flow is not the steam flow.
- Using gauge pressure as absolute.
Assumptions and limits
- No heat loss from the casing; steady flow.
- Water side single-phase; a warning is given if it reaches saturation, and for a temperature cross at either end.
- The water-side pressure drop is neglected: the outlet saturation temperature is taken at the inlet pressure, which slightly overstates the approach.
- At or above the critical pressure (220.64 bar) there is no saturation temperature, so the approach is not shown.
References
- IAPWS R7-97(2012) IF97
- first law heat balance
Questions and answers
How do I find the economiser water outlet temperature?
The heat the gas gives up goes into the water. 37 kg/s of gas cooling from 350 to 180 °C gives 6.79 MW; 14.2 kg/s of water at 70 bar(a) entering at 150 °C leaves at 256 °C, 30 K below saturation.
What approach to saturation should an economiser have?
Non-steaming economisers are usually designed to leave the water 20–40 K below saturation at full load, so that it does not steam at part load or in upsets. A steaming economiser is designed for it on purpose.
Which gas specific heat?
The mean value between the two gas temperatures, about 1.05–1.10 kJ/(kg·K) for coal flue gas. The gas properties calculator gives it from the gas analysis.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.