Uninsulated Stack or Duct: Wall Temperature and Heat Loss

Wall temperature, heat loss and exit gas temperature of an uninsulated steel stack or round duct, from gas flow, wind and emissivity.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: Ganapathy Q4.57 case: 110,000 lb/h at 410 °F, 48 in, 50 ftSmall duct 0.6 m, 180 °C, windy

Results

Wall below about 140 °C: check against the acid dew point of the flue gas; consider insulation.

Steel wall resistance neglected; one segment. Split a tall stack into segments for accuracy.

Gas-side coefficient25.401W/(m²·K)
Wall temperature (average)78.615°C
Heat loss per outer area2,063.2W/m²
Total heat loss119.00kW
Gas outlet temperature142.93°C

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Ganapathy Q4.57 case: 110,000 lb/h at 410 °F, 48 in, 50 ft. The inputs, in the units selected above:

InputValue
Gas flow49,895 kg/h
Gas inlet temperature210.00 °C
Inside diameter1,219.2 mm
Wall thickness25.400 mm
Length (height)15.240 m
Ambient temperature21.110 °C
Wind speed0.50800 m/s
Outer surface emissivity90.000 %
Gas viscosity0.024000 cP
Gas thermal conductivity0.035000 W/(m·K)
Gas specific heat1.0800 kJ/(kg·K)

Applying the formula below gives:

ResultValue
Gas-side coefficient24.652 W/(m²·K)
Wall temperature (average)125.19 °C
Heat loss per outer area1,915.1 W/m²
Total heat loss116.45 kW
Gas outlet temperature202.22 °C

Open this example in the calculator and change any input.

Formula

\(q = \sigma\varepsilon(T_w^4 - T_a^4) + 1.947(T_w - T_a)^{1.25}\sqrt{\frac{196.85V + 69}{69}}, \quad (T_g - T_w)h_c\frac{d_i}{d_o} = q\)

\(h_c = 0.023Re^{0.8}Pr^{0.4}\frac{k}{d_i}, \quad T_{g2} = T_{g1} - \frac{q\pi d_oH}{Wc_p}\)

Variables

Symbol Meaning SI unit
\(W\) Gas flow kg/s
\(T_{g1}\) Gas inlet temperature K
\(d_i\) Inside diameter m
\(t\) Wall thickness m
\(H\) Length (height) m
\(T_a\) Ambient temperature K
\(V\) Wind speed m/s
\(\varepsilon\) Outer surface emissivity -
\(\mu\) Gas viscosity Pa·s
\(k\) Gas thermal conductivity W/(m·K)
\(c_p\) Gas specific heat J/(kg·K)
\(h_c\) Gas-side coefficient W/(m²·K)
\(T_w\) Wall temperature (average) K
\(q\) Heat loss per outer area W/m²
\(Q\) Total heat loss W
\(T_{g2}\) Gas outlet temperature K

Method and standards

Ganapathy's casing-loss equation (radiation plus natural and wind convection, Eq. 106) converted to SI through FireCAD's unit factors, with a Dittus–Boelter gas film (exponent 0.4, as Ganapathy uses). The wall and gas outlet temperatures are solved together over one segment.

Where it is used

  • Stack and duct design for low-temperature flue gas.
  • Deciding on insulation.

Common mistakes

  • Using the gas temperature as the wall temperature.
  • Ignoring wind.

Assumptions and limits

  • Thin steel wall; single segment; turbulent gas flow (a warning below Re 10 000).
  • The Dittus–Boelter exponent 0.4 is the heating form; for gas being cooled the classical exponent is 0.3, about 10 % lower h_c at Pr 0.7, which would give a slightly colder wall. Gas radiation to the wall is neglected.
  • The gas must stay above ambient over the length, and the wall and gas temperatures must converge; otherwise the calculation stops and asks for a shorter segment.

References

  • Ganapathy
  • Steam Plant Calculations Manual
  • 2nd ed. (Marcel Dekker, 1993)
  • Q4.57 (stack and duct wall temperature with and without insulation) and Eq. (106) for casing heat loss; gas-side coefficient by Dittus–Boelter

Questions and answers

Why does wall temperature matter?

If the inner wall falls below the acid dew point, sulfuric acid condenses and corrodes the steel even when the gas is well above it.

Why is the wall much colder than the gas?

The gas film coefficient is low (15–30 W/(m²·K)) compared with radiation and wind losses outside an uninsulated wall.

What do the defaults represent?

Ganapathy's case: 110,000 lb/h at 410 °F in a 48 in stack, 50 ft long, 1 in thick, 70 °F ambient.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.