FireCADCalc

Stack Height from SO₂ Emission (CPCB Formula H = 14 Q^0.3)

Sulphur dioxide emission rate from fuel firing and sulphur content, and the minimum physical stack height by the Indian rule H = 14 Q^0.3 (Q in kg/h of SO₂).

Thermal power plantSugar mill and cogenerationChemical and fertiliserPulp and paperBoilerStack and chimney

Inputs

Examples: 2 t/h coal, 0.5 % S, 110 % ratingFurnace oil 1.5 t/h, 3.5 % SCFBC 25 t/h coal, 0.45 % S, 80 % captured by limestone

Results

The same schedule also sets fixed stack heights by boiler size and plant rating, and the consent of your State Pollution Control Board may set more; check the current notification.

SO₂ emission rate49.452kg/h
Minimum physical stack height45.122m

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 2 t/h coal, 0.5 % S, 110 % rating. The inputs, in the units selected above:

InputValue
Fuel fired at rated capacity2,000.0 kg/h
Sulphur in the fuel, as fired0.50000 %
Sulphur retained in the ash or by a scrubber0 %
Load multiplier for Q (the rule takes 110 % of rated capacity)1.1000 -

Applying the formula below gives:

ResultValue
SO₂ emission rate21.979 kg/h
Minimum physical stack height35.378 m

Open this example in the calculator and change any input.

Formula

\(Q = \dot m_F\, S\, (1 - r)\, k\, \frac{M_{SO_2}}{M_S}\)

\(H = 14\, Q^{0.3} \quad (H\ \text{in m},\ Q\ \text{in kg/h})\)

Variables

Symbol Meaning SI unit
\(\dot m_F\) Fuel fired at rated capacity kg/s
\(S\) Sulphur in the fuel, as fired -
\(r\) Sulphur retained in the ash or by a scrubber -
\(k\) Load multiplier for Q (the rule takes 110 % of rated capacity) -
\(Q\) SO₂ emission rate kg/s
\(H\) Minimum physical stack height m
\(M_{SO_2}, M_S\) Molar masses of SO₂ and sulphur kg/kmol

Method and standards

Each kilogram of sulphur burnt gives 64.058/32.06 kg of SO₂ (IUPAC molar masses). Retention in ash or capture by limestone or a scrubber is deducted, and the rule takes the emission at 110 % of rated capacity. The height formula is the statutory one of the Environment (Protection) Rules 1986.

Where it is used

  • Fixing stack height for a new boiler or DG set application.
  • Checking an existing stack after a fuel change.
  • Preparing consent-to-establish documents.

Common mistakes

  • Entering Q in g/s or t/h instead of kg/h.
  • Using sulphur on a dry basis while the firing rate is as fired.
  • Forgetting the fixed minimum heights in the same schedule.

Assumptions and limits

  • Statutory formula; check the current notification and consent conditions.
  • No credit for dispersion modelling.

References

  • Environment (Protection) Rules 1986
  • Schedule VI
  • Part D (Government of India)

Questions and answers

What height does H = 14 Q^0.3 give for a 2 t/h coal boiler?

With 0.5 % sulphur and Q taken at 110 % of rating, SO₂ is about 22 kg/h and the stack must be at least 35 m.

Where does the formula come from?

Schedule VI of the Environment (Protection) Rules 1986 sets H = 14 Q^0.3, with H the physical stack height in metres and Q the SO₂ emission in kg/h.

Is the formula the only rule?

No: the same schedule also gives fixed heights by boiler size and for power plants, and the State Pollution Control Board's consent may ask for more. Use the larger.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.