Worked example
Example: 2 t/h coal, 0.5 % S, 110 % rating. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Fuel fired at rated capacity | 2,000.0 kg/h |
| Sulphur in the fuel, as fired | 0.50000 % |
| Sulphur retained in the ash or by a scrubber | 0 % |
| Load multiplier for Q (the rule takes 110 % of rated capacity) | 1.1000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| SO₂ emission rate | 21.979 kg/h |
| Minimum physical stack height | 35.378 m |
Open this example in the calculator and change any input.
Formula
\(Q = \dot m_F\, S\, (1 - r)\, k\, \frac{M_{SO_2}}{M_S}\)
\(H = 14\, Q^{0.3} \quad (H\ \text{in m},\ Q\ \text{in kg/h})\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_F\) | Fuel fired at rated capacity | kg/s |
| \(S\) | Sulphur in the fuel, as fired | - |
| \(r\) | Sulphur retained in the ash or by a scrubber | - |
| \(k\) | Load multiplier for Q (the rule takes 110 % of rated capacity) | - |
| \(Q\) | SO₂ emission rate | kg/s |
| \(H\) | Minimum physical stack height | m |
| \(M_{SO_2}, M_S\) | Molar masses of SO₂ and sulphur | kg/kmol |
Method and standards
Each kilogram of sulphur burnt gives 64.058/32.06 kg of SO₂ (IUPAC molar masses). Retention in ash or capture by limestone or a scrubber is deducted, and the rule takes the emission at 110 % of rated capacity. The height formula is the statutory one of the Environment (Protection) Rules 1986.
Where it is used
- Fixing stack height for a new boiler or DG set application.
- Checking an existing stack after a fuel change.
- Preparing consent-to-establish documents.
Common mistakes
- Entering Q in g/s or t/h instead of kg/h.
- Using sulphur on a dry basis while the firing rate is as fired.
- Forgetting the fixed minimum heights in the same schedule.
Assumptions and limits
- Statutory formula; check the current notification and consent conditions.
- No credit for dispersion modelling.
References
- Environment (Protection) Rules 1986
- Schedule VI
- Part D (Government of India)
Questions and answers
What height does H = 14 Q^0.3 give for a 2 t/h coal boiler?
With 0.5 % sulphur and Q taken at 110 % of rating, SO₂ is about 22 kg/h and the stack must be at least 35 m.
Where does the formula come from?
Schedule VI of the Environment (Protection) Rules 1986 sets H = 14 Q^0.3, with H the physical stack height in metres and Q the SO₂ emission in kg/h.
Is the formula the only rule?
No: the same schedule also gives fixed heights by boiler size and for power plants, and the State Pollution Control Board's consent may ask for more. Use the larger.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.