FireCADCalc

SO₃ from SO₂ Conversion

SO₃ in flue gas from the SO₂ concentration and the share converted to SO₃, by mass and by volume, for acid dew point and ammonium bisulphate checks.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolEconomiser and air preheaterStack and chimney

Inputs

Examples: 1500 mg/Nm3, 1.5 %Oil firing 3 %

Results

A few ppm of SO₃ raise the acid dew point sharply: use the SO₃ by volume in the acid dew point calculator, converted to a wet basis first (dry value × (1 − water vapour fraction)), because that calculator works on wet gas.

SO₃ (dry, normal)93.732mg/Nm³
SO₃ by volume (dry)26.243ppm
SO₂ by volume (dry, as entered, before conversion)874.75ppm

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 1500 mg/Nm3, 1.5 %. The inputs, in the units selected above:

InputValue
SO₂ (dry, normal)1,500.0 mg/Nm³
Share of SO₂ converted to SO₃1.5000 %

Applying the formula below gives:

ResultValue
SO₃ (dry, normal)28.120 mg/Nm³
SO₃ by volume (dry)7.8728 ppm
SO₂ by volume (dry, as entered, before conversion)524.85 ppm

Open this example in the calculator and change any input.

Formula

\(c_{SO_3} = c_{SO_2} f \frac{M_{SO_3}}{M_{SO_2}}, \quad y = \frac{c}{M}V_m\)

Variables

Symbol Meaning SI unit
\(c_{SO_2}\) SO₂ (dry, normal) kg/m³
\(f\) Share of SO₂ converted to SO₃ -
\(c_{SO_3}\) SO₃ (dry, normal) kg/m³
\(y_{SO_3}\) SO₃ by volume (dry) -
\(y_{SO_2}\) SO₂ by volume (dry, as entered, before conversion) -

Method and standards

Mass balance with IUPAC molar masses: the SO₃ formed is the converted share of the SO₂ entered; volume fractions on the molar volume at 0 °C and 1 atm.

Where it is used

  • Cold-end corrosion studies.
  • SCR design.

Common mistakes

  • SO₂ ppm entered as mg/Nm³.

Assumptions and limits

  • Dry, normal basis. The SO₂ entered is taken as the SO₂ before conversion; its volume fraction is not reduced by the share converted.
  • For the acid dew point calculator, which works on wet gas, multiply the dry SO₃ fraction by (1 − water vapour fraction).

References

  • Mass balance with IUPAC molar masses; ppm on the molar volume at 0 °C
  • 1 atm

Questions and answers

What conversion?

Around 1–3 % in boilers; vanadium in oil ash and SCR catalysts raise it.

Why does SO₃ matter?

It sets the acid dew point and corrosion of the air heater cold end.

With SCR?

SO₃ and ammonia slip form ammonium bisulphate deposits.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.