Worked example
Example: 100 000 Nm3/h, 400 mg/Nm3. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Flue gas flow (dry, normal) | 100,000 Nm³/h |
| NOx at the inlet (as NO₂, dry) | 400.00 mg/Nm³ |
| NOx reduction wanted | 40.000 % |
| Normalised stoichiometric ratio | 1.8000 - |
| Urea strength of the solution | 40.000 % |
| Solution density | 1,110.0 kg/m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| NOx at the inlet (as NO₂) | 40.000 kg/h |
| NOx removed (as NO₂) | 16.000 kg/h |
| Urea (100 %) | 46.995 kg/h |
| Urea solution | 105.85 L/h |
| Reagent utilisation η/NSR | 22.222 % |
Open this example in the calculator and change any input.
Formula
\(\dot n_{NO_x} = \frac{\dot V_n c_{NO_x}}{M_{NO_2}}, \quad \dot m_u = \dot n_{NO_x}\frac{NSR}{2}M_{urea}, \quad \dot V_s = \frac{\dot m_u}{w\rho_s}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V_n\) | Flue gas flow (dry, normal) | Nm³/s |
| \(c_{NO_x}\) | NOx at the inlet (as NO₂, dry) | kg/m³ |
| \(\eta\) | NOx reduction wanted | - |
| \(NSR\) | Normalised stoichiometric ratio | - |
| \(w\) | Urea strength of the solution | - |
| \(\rho_s\) | Solution density | kg/m³ |
| \(\dot m_{NO_x}\) | NOx at the inlet (as NO₂) | kg/s |
| \(\Delta\dot m_{NO_x}\) | NOx removed (as NO₂) | kg/s |
| \(\dot m_u\) | Urea (100 %) | kg/s |
| \(\dot V_s\) | Urea solution | m³/s |
| \(u\) | Reagent utilisation η/NSR | - |
Method and standards
Stoichiometry: the urea dose follows from the inlet NOx (as NO₂) and the NSR, at two NH₃ equivalents per mole of urea. The reduction wanted does not change the dose; it gives the NOx removed and the utilisation η/NSR, and a warning appears when that would exceed 100 %.
Where it is used
- SNCR system sizing.
- Reagent budgets.
Common mistakes
- NOx as NO instead of NO₂.
- Wet gas flow with dry concentration.
Assumptions and limits
- Dry, normal basis throughout.
- The solution density is not linked to the strength: change it when you change the strength.
References
- Stoichiometry CO(NH₂)₂ + 2 NO + ½ O₂ → 2 N₂ + CO₂ + 2 H₂O (one mole of urea per two of NO); NSR as NH₃ equivalents per mole of NOx
Questions and answers
What is NSR?
Moles of reducing agent, as NH₃ equivalents, per mole of NOx entering; urea counts double.
Why is NSR above the reduction?
SNCR utilisation is poor: reagent is lost to oxidation and slip, so NSR of 1.5–2.5 is common.
Urea or ammonia?
Urea is safer to store; aqueous ammonia gives a slightly different temperature window.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.