Worked example
Example: Coal boiler NOx 350 ppm at 7.5 % O2, EU IED 6 %. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Pollutant | NOx as NO₂ |
| Measured value in | ppm by volume |
| Measured concentration, ppm | 350.00 ppm |
| Measured concentration, mg/Nm³ | 0 mg/Nm³ |
| Measured O₂ | 7.5000 % |
| Reference O₂ of the limit | 6.0000 % |
| O₂ in air used by the rule | 21.000 % |
| Water vapour in the sample (0 for a dry analyser) | 0 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| At reference O₂, dry, mg/Nm³ | 798.20 mg/Nm³ |
| At reference O₂, dry, ppm | 388.89 ppm |
| Measured, dry basis, mg/Nm³ | 718.38 mg/Nm³ |
| Measured, dry basis, ppm | 350.00 ppm |
| Measured O₂, dry basis | 7.5000 % |
| Correction factor | 1.1111 |
| Molar mass used for ppm ↔ mg/Nm³ | 46.005 kg/kmol |
Open this example in the calculator and change any input.
Formula
Dry basis (for a hot-wet analyser):
\(c_d = \frac{c_m}{1 - y_{H_2O}} \qquad O_{2,d} = \frac{O_{2,m}}{1 - y_{H_2O}}\)
Correction to the reference O₂ (EU IED Annex VI Part 2):
\(k = \frac{O_{2,air} - O_{2,ref}}{O_{2,air} - O_{2,d}} \qquad c_{ref} = k\,c_d\)
Volume to mass concentration at 0 °C and 101.325 kPa:
\(c\,[\text{mg/Nm}^3] = c\,[\text{ppm}] \times \frac{M}{V_{m,N}} \qquad V_{m,N} = 22.414\ \text{m}^3/\text{kmol}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{species}\) | pollutant: NOx as NO₂, SO₂, CO, NO or dust | – |
| \(\text{basis}\) | measured value in ppm or mg/Nm³ | – |
| \(c_m\) | measured concentration, ppm by volume | – |
| \(c_{m,mg}\) | measured concentration, mg/Nm³ (SI: kg per normal m³ at 0 °C) | kg/m³ |
| \(O_{2,m}\) | measured O₂ | – |
| \(O_{2,ref}\) | reference O₂ of the emission limit | – |
| \(O_{2,air}\) | O₂ in air used by the rule (21 % or 20.9 %) | – |
| \(y_{H_2O}\) | water vapour in the sample, 0 for a dry analyser | – |
| \(c_{ref}\) | concentration at reference O₂, dry, mg/Nm³ | kg/m³ |
| \(c_{ref,ppm}\) | concentration at reference O₂, dry, ppm | – |
| \(c_{d}\) | measured concentration, dry basis, mg/Nm³ | kg/m³ |
| \(c_{d,ppm}\) | measured concentration, dry basis, ppm | – |
| \(O_{2,d}\) | measured O₂, dry basis | – |
| \(k\) | correction factor | – |
| \(M\) | molar mass of the pollutant (NO₂ 46.005, SO₂ 64.058, CO 28.010, NO 30.006) | kg/kmol |
| \(V_{m,N}\) | molar volume of an ideal gas at 0 °C, 101.325 kPa | m³/kmol |
Method and standards
EU Directive 2010/75/EU (Industrial Emissions Directive), Annex VI Part 2, gives the correction E_S = (21 − O_S)/(21 − O_M) · E_M on a dry basis at 273.15 K and 101.3 kPa, with reference O₂ of 6 % for solid fuels, 3 % for liquid and gaseous fuels and 15 % for gas turbines and engines. India's CPCB norms for thermal power plants (2015) are stated at 6 % O₂ dry. Molar masses from IUPAC atomic weights; the molar volume is R·273.15/101 325 (CODATA 2018).
Where it is used
- Reporting emissions at the reference O2 of the permit.
- Comparing stack readings at different excess air.
- Continuous emission monitoring calculations.
Common mistakes
- Correcting a wet reading with a dry O2.
- Using the wrong reference O2 for the fuel.
- Correcting when the limit is already at actual O2.
Assumptions and limits
- Concentration and O₂ are measured on the same basis (both dry, or both wet with the water content entered).
- NOx is expressed as NO₂, as the IED and CPCB limits require.
- Normal conditions are 0 °C and 101.325 kPa; for limits at other reference conditions the mg/Nm³ figures differ. US EPA limits are at 20 °C (68 °F): a value here is about 7 % higher than the same gas expressed per dry standard m³ at 20 °C (multiply by 273.15/293.15 to convert).
- The correction is not meant for O₂ near 21 %; above about 18 % small O₂ errors dominate.
References
- EU Directive 2010/75/EU (IED) Annex VI Part 2
- India CPCB emission norms for thermal power plants (2015)
- US EPA Method 19 (20.9 % O₂ option)
Questions and answers
How do I correct an emission to 6 % O₂?
Multiply the dry concentration by (21 − 6)/(21 − O₂ measured). NOx of 350 ppm at 7.5 % O₂ becomes 389 ppm at 6 %, or 798 mg/Nm³ as NO₂.
How do I convert ppm to mg/Nm³?
mg/Nm³ = ppm × M / 22.414, with M the molar mass in g/mol and Nm³ at 0 °C and 101.325 kPa. For NOx expressed as NO₂, M = 46.005, so 1 ppm = 2.053 mg/Nm³; for SO₂ 1 ppm = 2.858 mg/Nm³.
Why 21 % and not 20.95 %?
The EU Industrial Emissions Directive and India CPCB practice write the correction with 21 %; US EPA Method 19 uses 20.9 %. The calculator takes the value of the rule you report against.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.