Worked example
Example: Indian coal, 25 % excess air, ESP 99.8 %, reference 6 %. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Carbon | 45.000 % |
| Hydrogen | 3.5000 % |
| Oxygen | 5.0000 % |
| Nitrogen | 1.0000 % |
| Sulphur | 0.50000 % |
| Ash | 35.000 % |
| Moisture | 10.000 % |
| Fuel firing rate | 12,000 kg/h |
| Excess air | 25.000 % |
| Air humidity (kg water per kg dry air) | 0.013000 kg/kg |
| Share of the residue leaving as fly ash | 80.000 % |
| Carbon in the residue | 2.0000 % |
| Dust collector efficiency | 99.800 % |
| Reference O₂ of the limit | 6.0000 % |
| O₂ in air used by the rule | 21.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Dust at the stack, dry, at reference O₂ | 88.006 mg/Nm³ |
| Dust at the stack, dry, at actual O₂ | 97.987 mg/Nm³ |
| Dust at the collector inlet, dry | 48,993 mg/Nm³ |
| Dust emitted | 6.8571 kg/h |
| Dry flue gas, normal volume | 69,980 Nm³/h |
| O₂ in dry flue gas | 4.2989 % |
| Correction factor to reference O₂ | 0.89814 |
Open this example in the calculator and change any input.
Formula
\(c_{in} = \frac{A\,x_f / (1 - c_r)}{v_{dry}} \qquad c_{out} = c_{in}(1 - \eta_c) \qquad k = \frac{O_{2,air} - O_{2,ref}}{O_{2,air} - O_{2,d}} \qquad c_{ref} = k\,c_{out}\)
\(\dot V_{dry,N} = \dot m_f\,v_{dry} \qquad \dot m_d = \dot m_f\,\frac{A\,x_f}{1 - c_r}\,(1 - \eta_c)\)
\(v_{dry}\) is the dry flue gas per kg of fuel at 0 °C and 101.325 kPa, and \(O_{2,d}\) its O₂, both from the exact-ratio combustion balance.
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(C\), \(H\), \(O\), \(N\), \(S\) | carbon, hydrogen, oxygen, nitrogen, sulphur in the fuel as fired | – |
| \(A\) | ash | – |
| \(M\) | moisture | – |
| \(\dot m_f\) | fuel firing rate | kg/s |
| \(EA\) | excess air | – |
| \(\omega\) | air humidity | kg/kg |
| \(x_f\) | share of the residue leaving as fly ash | – |
| \(c_r\) | carbon in the residue | – |
| \(\eta_c\) | dust collector efficiency | – |
| \(O_{2,ref}\) | reference O₂ of the limit | – |
| \(O_{2,air}\) | O₂ in air used by the rule | – |
| \(c_{ref}\) | dust at the stack, dry, at reference O₂ | kg/m³ |
| \(c_{out}\) | dust at the stack, dry, at actual O₂ | kg/m³ |
| \(c_{in}\) | dust at the collector inlet, dry | kg/m³ |
| \(\dot m_d\) | dust emitted | kg/s |
| \(\dot V_{dry,N}\) | dry flue gas, normal volume | Nm³/s |
| \(O_{2,d}\) | O₂ in dry flue gas | – |
| \(k\) | correction factor to reference O₂ | – |
| \(v_{dry}\) | dry flue gas per kg of fuel, normal | m³/kg |
Method and standards
Dry flue gas volume from the exact-ratio combustion balance with ASME PTC 4-2013 air; fly ash from the ash balance; the O₂ correction of EU IED 2010/75/EU Annex VI, the same form Indian limits use.
Where it is used
- Estimating stack dust for permits and design.
- Sizing the dust collector efficiency needed.
- Comparing fuels by dust load.
Common mistakes
- Using total ash instead of fly ash.
- Mixing wet and dry or actual and normal gas volumes.
- Forgetting the O2 reference of the emission limit.
Assumptions and limits
- All fly ash reaches the collector; deposits in the boiler and economiser hoppers are counted as bottom ash.
- Sulphate, unburned carbon in fly ash beyond the residue carbon, and sorbent are not added.
- Normal conditions 0 °C and 101.325 kPa, dry basis.
- The residue carbon raises the fly-ash mass, but the combustion balance burns all fuel carbon; the small inconsistency (about 1–2 % of the carbon at usual values) slightly overstates the gas volume.
References
- Exact-ratio combustion balance with ASME PTC 4-2013 air; EU IED 2010/75/EU Annex VI (O₂ correction, also used in Indian practice)
Questions and answers
What is the dust load before the ESP?
Fly ash per kg of fuel divided by the dry flue gas per kg of fuel. A 35 %-ash Indian coal at 25 % excess air (the default is 20 %) with 80 % fly ash gives about 49 g/Nm³ dry at the collector inlet.
What efficiency does the collector need?
To meet 50 mg/Nm³ at 6 % O₂ from 49 g/Nm³ at 4.3 % O₂ the collector must exceed about 99.9 %. The calculator shows the stack value for the efficiency you enter.
Why correct to reference O₂?
Limits are stated at a reference O₂ so that dilution with excess air does not lower the reading. The correction uses the same formula as the emission correction calculator.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.