Cyclone Cut Size and Collection Efficiency (Lapple)

Cut size (d50) of a cyclone dust collector by the Lapple method from its inlet and body dimensions and gas flow, with the collection efficiency for a chosen particle size.

Thermal power plantSugar mill and cogenerationChemical and fertiliserPulp and paperBoilerDust collector (ESP, bag filter, cyclone)

Inputs

Examples: 3 m³/s, inlet 250 × 500 mm, 10 µm dustBoiler fly ash 8 m³/s at 180 °C, 5 µmWood dust 1.5 m³/s, 20 µm

Results

Inlet velocity28.571m/s
Effective number of turns5.5714
Cut size (50 % collected)6.4574µm
Collection efficiency for the particle size90.560%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 3 m³/s, inlet 250 × 500 mm, 10 µm dust. The inputs, in the units selected above:

InputValue
Gas flow at cyclone conditions10,800 m³/h
Inlet width250.00 mm
Inlet height500.00 mm
Length of the cylindrical body2.0000 m
Length of the cone2.0000 m
Gas dynamic viscosity2.5000e-05 Pa·s
Particle density2,000.0 kg/m³
Gas density0.85000 kg/m³
Particle size to evaluate10.000 µm

Applying the formula below gives:

ResultValue
Inlet velocity24.000 m/s
Effective number of turns6.0000
Cut size (50 % collected)5.5766 µm
Collection efficiency for the particle size76.279 %

Open this example in the calculator and change any input.

Formula

\(V_i = \frac{Q}{W H}\)

\(N_e = \frac{1}{H}\left(L_b + \frac{L_c}{2}\right)\)

\(d_{50} = \sqrt{\frac{9 \mu W}{2 \pi N_e V_i (\rho_p - \rho_g)}}\)

\(\eta_d = \frac{1}{1 + (d_{50}/d_p)^2}\)

Variables

Symbol Meaning SI unit
\(Q\) gas flow at cyclone conditions m³/s
\(W\) inlet width m
\(H\) inlet height m
\(L_b\) length of the cylindrical body m
\(L_c\) length of the cone m
\(\mu\) gas dynamic viscosity Pa·s
\(\rho_p\) particle density kg/m³
\(\rho_g\) gas density kg/m³
\(d_p\) particle size m
\(V_i\) inlet velocity m/s
\(N_e\) effective number of turns -
\(d_{50}\) cut size m
\(\eta_d\) collection efficiency for d_p -

Method and standards

Lapple's model treats the outer vortex as a settling chamber: particles must cross the inlet width during N_e turns. The cut size is the diameter collected with 50 % efficiency; the fractional efficiency curve 1/(1 + (d50/d)²) is the fit to Lapple's curve given by Chopey.

Where it is used

  • Sizing a pre-collector ahead of a bag filter or ESP.
  • Checking a boiler multicyclone after a fuel change.
  • Comparing cyclone designs.

Common mistakes

  • Using normal (Nm³) flow instead of actual flow at gas temperature.
  • Using bulk density of the dust instead of particle density.
  • Expecting good collection of particles well below the cut size.

Assumptions and limits

  • Standard tangential-inlet cyclone of the Lapple type (inlet about half the body diameter high and a quarter wide). The dimensions are not checked against that geometry; for other proportions the result is only indicative.
  • The 10–30 m/s inlet velocity warning is a common design range, not a limit from the method.
  • Efficiency curve for a single particle size; integrate over the size distribution for the overall efficiency.
  • Re-entrainment and hopper leakage not included.

References

  • Lapple (1951) cut size
  • Chopey
  • Handbook of Chemical Engineering Calculations (efficiency curve)

Questions and answers

What is the cut size of a cyclone?

The particle size collected with 50 % efficiency. For a 250 × 500 mm inlet taking 3 m³/s with 2 m body and 2 m cone, it is about 5.6 µm for 2 000 kg/m³ dust.

How efficient is a cyclone for 10 µm dust?

By the Lapple curve η = 1/(1 + (d50/d)²): about 76 % in the example above.

How do I make a cyclone collect finer dust?

Raise the inlet velocity (within pressure drop limits), use a narrower inlet or a longer body and cone, or use several small cyclones in parallel.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.