Self-Priming Pump: Time to Evacuate the Suction Line

Time a self-priming pump takes to draw the air out of its suction line against a suction lift, from its air-handling capacity and the line volume.

Inputs

Examples: Illustrative DN 100 line, 4 m liftLong DN 150 line, 6 m liftShort DN 50 line, 2 m lift

Accepted: 10 to 1,000 mm
Accepted: 0.1 to 500 m
Accepted: 0 to 1,000 L
Accepted: 0 to 9.5 m
Accepted: 0.0036 to 3,600 m³/h
Accepted: 0.5 to 1.1 bar
Accepted: 500 to 2,000 kg/m³

Results

While priming, the pump acts as a vacuum pump on a fixed volume: the pressure falls as p = p_a e^(−St/V), and the liquid reaches the pump when the pressure is p_a − ρgh_s, so t = (V/S) ln[p_a/(p_a − ρgh_s)]. The rising liquid column shrinks the air volume, so the real time is a little shorter; leaks at joints and the shaft seal make it longer, or stop priming altogether. Makers rate self-priming pumps by the time to prime a given lift and pipe size; the air-handling capacity here is the figure that matches it.

Air volume to evacuate385.01L
Pressure needed at the pump to lift the liquid0.42603bar
Priming time30.022s

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative DN 100 line, 4 m lift. The inputs, in the units selected above:

InputValue
Suction pipe inside diameter102.30 mm
Suction pipe length8.0000 m
Air volume in the pump casing5.0000 L
Static suction lift4.0000 m
Air-handling capacity of the pump while priming25.000 m³/h
Atmospheric pressure1.0132 bar
Liquid density998.00 kg/m³

Applying the formula below gives:

ResultValue
Air volume to evacuate70.755 L
Pressure needed at the pump to lift the liquid0.62177 bar
Priming time4.9757 s

Open this example in the calculator and change any input.

Formula

\(t = \frac{V}{S}\ln\frac{p_a}{p_a - \rho g h_s}, \quad V = \frac{\pi d^2}{4}L + V_c\)

Variables

Symbol Meaning SI unit
\(d\) Suction pipe inside diameter m
\(L\) Suction pipe length m
\(V_c\) Air volume in the pump casing m³
\(h_s\) Static suction lift m
\(S\) Air-handling capacity of the pump while priming m³/s
\(p_a\) Atmospheric pressure Pa
\(\rho\) Liquid density kg/m³
\(V\) Air volume to evacuate m³
\(p_e\) Pressure needed at the pump to lift the liquid Pa
\(t\) Priming time s

Method and standards

Priming time.

Where it is used

  • Selecting self-priming pumps for sumps and tankers.
  • Checking priming of long suction lines.

Common mistakes

  • Ignoring the casing and fittings volume.
  • Using the liquid capacity instead of the air-handling capacity.

Assumptions and limits

  • Isothermal air; constant air-handling capacity; no leaks.

References

  • Isothermal evacuation of a fixed volume

Questions and answers

How long does a self-priming pump take to prime?

For the defaults, a 4 m lift through 8 m of DN 100 pipe with 25 m³/h of air handling takes about 5 s.

Why does my pump not prime?

Usually an air leak in the suction line or the seal, or a lift too high for the vapour pressure of the liquid.

What do the defaults represent?

An illustrative DN 100 suction line 8 m long, 4 m lift, 5 L casing air and 25 m³/h air handling.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Karassik, Messina, Cooper and Heald, Pump Handbook, 4th ed. (McGraw-Hill, 2008)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.