FireCADCalc

Overhead Water Tank and Pump Sizing for a Building

Overhead tank capacity, pump flow, pump power and daily energy for a building from population, per-capita demand, storage period, pumping hours and head.

Inputs

Examples: Illustrative 200-person buildingHostel, full day storageHospital, high demand

Accepted: 1 to 1,000,000
Accepted: 10 to 1,000
Accepted: 5 to 300 %
Accepted: 0.25 to 24 h
Accepted: 1 to 500 m
Accepted: 20 to 90 %

Results

Daily demand is people × litres per head. The overhead tank stores a share of it (often half a day in residences, more where supply is intermittent), and the pump must lift the whole day's demand in the pumping hours available. Power is ρgQH over the pump-set efficiency; small domestic pump-sets reach only 40–60 %. Add the head of the tank's height above the sump, pipe friction and a few metres of margin.

Daily demand102,000L
Overhead tank capacity76,500L
Pump flow170.00L/min
Pump input power1.7065kW
Energy per day17.065kWh

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 200-person building. The inputs, in the units selected above:

InputValue
Number of people served200.00 -
Water demand per person per day (litres)135.00 -
Storage in the overhead tank (share of a day's demand)50.000 %
Pumping hours per day6.0000 h
Total pump head (static lift plus friction)30.000 m
Pump-set efficiency55.000 %

Applying the formula below gives:

ResultValue
Daily demand27,000 L
Overhead tank capacity13,500 L
Pump flow75.000 L/min
Pump input power0.66730 kW
Energy per day4.0038 kWh

Open this example in the calculator and change any input.

Formula

\(Q_d = N q, \quad V = f_s Q_d, \quad \dot V_p = \frac{Q_d}{t_p}, \quad P = \frac{\rho g \dot V_p H}{\eta}\)

Variables

Symbol Meaning SI unit
\(N\) Number of people served -
\(q\) Water demand per person per day (litres) -
\(f_s\) Storage in the overhead tank (share of a day's demand) -
\(t_p\) Pumping hours per day s
\(H\) Total pump head (static lift plus friction) m
\(\eta\) Pump-set efficiency -
\(Q_d\) Daily demand m³
\(V\) Overhead tank capacity m³
\(\dot V_p\) Pump flow m³/s
\(P\) Pump input power W
\(E\) Energy per day J

Method and standards

Overhead tank.

Where it is used

  • Apartments, hostels, hospitals and offices.
  • Replacing or upgrading building pumps.

Common mistakes

  • Sizing the pump for the tank volume instead of the daily demand.
  • Ignoring friction in long rising mains.

Assumptions and limits

  • Uniform demand; pumping hours as entered.

References

  • Water demand and pumping balance

Questions and answers

What size of overhead tank does a 200-person building need?

With 135 L per person and half a day of storage, 13,500 litres.

How big a pump fills it?

27,000 L in 6 h is 75 L/min; at 30 m head and 55 % efficiency about 0.67 kW (1 HP).

What do the defaults represent?

An illustrative 200-person building with 135 L per head, half a day of overhead storage, 6 h of pumping and 30 m head.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.