Worked example
Example: Illustrative 90 degree spray bar. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Rated flow | 2.0000 L/min |
| Rated pressure | 3.0000 bar |
| Operating pressure | 4.0000 bar |
| Spray angle | 90.000 ° |
| Distance from nozzle to target | 0.30000 m |
| Width to cover | 2.0000 m |
| Overlap between neighbouring sprays | 30.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Flow at the operating pressure | 2.3094 L/min |
| Coverage width of one nozzle | 600.00 mm |
| Nozzle spacing | 420.00 mm |
| Nozzles needed across the width | 5.0000 |
| Total flow | 11.547 L/min |
Open this example in the calculator and change any input.
Formula
\(Q_2 = Q_1\sqrt{\frac{p_2}{p_1}}, \quad w_c = 2h\tan\frac\theta2, \quad n = \left\lceil\frac{W}{w_c(1 - f_o)}\right\rceil\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q_1\) | Rated flow | m³/s |
| \(p_1\) | Rated pressure | Pa |
| \(p_2\) | Operating pressure | Pa |
| \(\theta\) | Spray angle | rad |
| \(h\) | Distance from nozzle to target | m |
| \(W\) | Width to cover | m |
| \(f_o\) | Overlap between neighbouring sprays | - |
| \(Q_2\) | Flow at the operating pressure | m³/s |
| \(w_c\) | Coverage width of one nozzle | m |
| \(s\) | Nozzle spacing | m |
| \(n\) | Nozzles needed across the width | - |
| \(Q_t\) | Total flow | m³/s |
Method and standards
Spray nozzles.
Where it is used
- Washing, cooling, coating and dust suppression.
- Spray header layout.
Common mistakes
- Assuming flow is proportional to pressure.
- Using the nominal angle at long distances.
Assumptions and limits
- Water-like liquid; nozzle in its normal pressure range.
References
- Orifice flow scaling and spray geometry
Questions and answers
How does flow change with pressure?
With the square root: doubling pressure gives 41 % more flow.
Why overlap the sprays?
Spray density falls off towards the edges, so overlapping evens out the coverage.
What do the defaults represent?
An illustrative 2 L/min at 3 bar nozzle run at 4 bar, 90° spray 300 mm from a 2 m wide target, 30 % overlap.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.