Worked example
Example: Illustrative DN100, 50 mm insulation, 5 C at -20 C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Pipe outside diameter | 114.00 mm |
| Insulation thickness | 50.000 mm |
| Insulation conductivity at mean temperature | 0.040000 W/(m·K) |
| Outside heat transfer coefficient | 15.000 W/(m²·K) |
| Maintain temperature | 5.0000 °C |
| Lowest ambient temperature | -20.000 °C |
| Safety factor | 1.2000 - |
| Cable output at the maintain temperature | 25.000 W/m |
| Circuit length | 100.00 m |
| Supply voltage | 230.00 V |
Applying the formula below gives:
| Result | Value |
|---|---|
| Heat loss per metre | 9.5970 W/m |
| Design heat per metre | 11.516 W/m |
| Tracer passes | 1.0000 |
| Circuit power | 2.5000 kW |
| Circuit current | 10.870 A |
Open this example in the calculator and change any input.
Formula
\(q' = \frac{T_m - T_a}{\frac{\ln(r_2/r_1)}{2\pi\lambda} + \frac{1}{2\pi r_2h_o}}, \quad n = \left\lceil\frac{k_sq'}{q_c}\right\rceil\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(D_o\) | Pipe outside diameter | m |
| \(t_{ins}\) | Insulation thickness | m |
| \(\lambda\) | Insulation conductivity at mean temperature | W/(m·K) |
| \(h_o\) | Outside heat transfer coefficient | W/(m²·K) |
| \(T_m\) | Maintain temperature | K |
| \(T_a\) | Lowest ambient temperature | K |
| \(k_s\) | Safety factor | - |
| \(q_c\) | Cable output at the maintain temperature | W/m |
| \(L\) | Circuit length | m |
| \(V\) | Supply voltage | V |
| \(q'\) | Heat loss per metre | W/m |
| \(q'_d\) | Design heat per metre | W/m |
| \(n\) | Tracer passes | - |
| \(P\) | Circuit power | W |
| \(I\) | Circuit current | A |
Method and standards
Trace heating.
Where it is used
- Freeze protection of water, fire and process lines.
- Temperature maintenance of viscous products.
Common mistakes
- Forgetting heat sinks at valves and supports.
- Using cable output at a lower temperature than maintained.
Assumptions and limits
- Steady state; dry insulation.
References
- Cylindrical insulation heat loss for trace heating
Questions and answers
How much heat does freeze protection need?
Typically 10–30 W/m for small insulated pipes in cold climates; process temperature maintenance needs more.
Why a safety factor?
Insulation gets wet or damaged and real conductivities exceed catalogue values.
What do the defaults represent?
An illustrative DN100 pipe with 50 mm insulation kept at 5 °C at −20 °C ambient, 25 W/m cable, 100 m circuit at 230 V.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Nayyar, Piping Handbook, 7th ed. (McGraw-Hill, 2000)