FireCADCalc

Fire Hydrant Flow Test: Flow Available at a Residual Pressure

Flow from a hydrant outlet by pitot reading and the flow available at a required residual pressure, from the static and test residual pressures.

Inputs

Examples: Illustrative hydrant testWeak mainStrong main, 4 in outlet

Accepted: 0.1 to 20 bar
Accepted: 0 to 20 bar
Accepted: 0.01 to 10 bar
Accepted: 20 to 200 mm
Accepted: 0.6 to 1
Accepted: 0 to 20 bar

Results

The pitot pressure in the free stream is its velocity pressure, so the outlet flow is c A √(2p/ρ) (the familiar 29.83 c d² √p in US units). The main pressure drop with flow follows the Hazen–Williams law, Δp ∝ Q^1.85, so the flow at another residual pressure scales as [(S − R_r)/(S − R_t)]^0.54. A test should drop the residual pressure by at least about 10 % of the static for a reliable extrapolation.

Test flow2,864.5L/min
Flow available at the required residual pressure5,246.2L/min
Same, in US gpm1,385.9US gal/min

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative hydrant test. The inputs, in the units selected above:

InputValue
Static pressure (gauge)6.0000 bar
Residual pressure during the test4.5000 bar
Pitot pressure at the outlet1.4000 bar
Outlet diameter63.500 mm
Outlet discharge coefficient0.90000 -
Residual pressure required1.4000 bar

Applying the formula below gives:

ResultValue
Test flow2,864.5 L/min
Flow available at the required residual pressure5,246.2 L/min
Same, in US gpm1,385.9 US gal/min

Open this example in the calculator and change any input.

Formula

\(Q_F = c\frac{\pi d^2}{4}\sqrt{\frac{2p_p}{\rho}}, \quad Q_R = Q_F\left(\frac{S - R_r}{S - R_t}\right)^{0.54}\)

Variables

Symbol Meaning SI unit
\(S\) Static pressure (gauge) Pa
\(R_t\) Residual pressure during the test Pa
\(p_p\) Pitot pressure at the outlet Pa
\(d\) Outlet diameter m
\(c\) Outlet discharge coefficient -
\(R_r\) Residual pressure required Pa
\(Q_F\) Test flow m³/s
\(Q_R\) Flow available at the required residual pressure m³/s
\(Q_{R,gpm}\) Same, in US gpm m³/s

Method and standards

Hydrant flow test.

Where it is used

  • Fire water supply assessment.
  • Checking municipal or plant mains for fire flow.

Common mistakes

  • Using a residual drop too small for a reliable extrapolation.
  • Using the wrong outlet coefficient.

Assumptions and limits

  • Water at about 20 °C; Hazen–Williams behaviour of the mains.

References

  • Hydrant flow test extrapolation with exponent 0.54 (Hazen–Williams)
  • as in NFPA 291 (method only)

Questions and answers

How much flow is available at 1.4 bar residual?

For the defaults, about 5,200 L/min, from a test flow of about 2,900 L/min at 4.5 bar residual.

Why the 0.54 exponent?

It is the inverse of the 1.85 exponent of Hazen–Williams friction.

What do the defaults represent?

An illustrative test: 6 bar static, 4.5 bar residual, 1.4 bar pitot on a 63.5 mm outlet, required residual 1.4 bar.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.