Worked example
Example: Illustrative hydrant test. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Static pressure (gauge) | 6.0000 bar |
| Residual pressure during the test | 4.5000 bar |
| Pitot pressure at the outlet | 1.4000 bar |
| Outlet diameter | 63.500 mm |
| Outlet discharge coefficient | 0.90000 - |
| Residual pressure required | 1.4000 bar |
Applying the formula below gives:
| Result | Value |
|---|---|
| Test flow | 2,864.5 L/min |
| Flow available at the required residual pressure | 5,246.2 L/min |
| Same, in US gpm | 1,385.9 US gal/min |
Open this example in the calculator and change any input.
Formula
\(Q_F = c\frac{\pi d^2}{4}\sqrt{\frac{2p_p}{\rho}}, \quad Q_R = Q_F\left(\frac{S - R_r}{S - R_t}\right)^{0.54}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(S\) | Static pressure (gauge) | Pa |
| \(R_t\) | Residual pressure during the test | Pa |
| \(p_p\) | Pitot pressure at the outlet | Pa |
| \(d\) | Outlet diameter | m |
| \(c\) | Outlet discharge coefficient | - |
| \(R_r\) | Residual pressure required | Pa |
| \(Q_F\) | Test flow | m³/s |
| \(Q_R\) | Flow available at the required residual pressure | m³/s |
| \(Q_{R,gpm}\) | Same, in US gpm | m³/s |
Method and standards
Hydrant flow test.
Where it is used
- Fire water supply assessment.
- Checking municipal or plant mains for fire flow.
Common mistakes
- Using a residual drop too small for a reliable extrapolation.
- Using the wrong outlet coefficient.
Assumptions and limits
- Water at about 20 °C; Hazen–Williams behaviour of the mains.
References
- Hydrant flow test extrapolation with exponent 0.54 (Hazen–Williams)
- as in NFPA 291 (method only)
Questions and answers
How much flow is available at 1.4 bar residual?
For the defaults, about 5,200 L/min, from a test flow of about 2,900 L/min at 4.5 bar residual.
Why the 0.54 exponent?
It is the inverse of the 1.85 exponent of Hazen–Williams friction.
What do the defaults represent?
An illustrative test: 6 bar static, 4.5 bar residual, 1.4 bar pitot on a 63.5 mm outlet, required residual 1.4 bar.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.