Worked example
Example: Illustrative 65 mm line, 500 L/min. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Flow | 500.00 L/min |
| Hose inside diameter | 65.000 mm |
| Hose length | 120.00 m |
| Lining roughness | 0.020000 mm |
| Nozzle height above the pump | 10.000 m |
| Nozzle pressure required | 5.0000 bar |
Applying the formula below gives:
| Result | Value |
|---|---|
| Velocity | 2.5113 m/s |
| Reynolds number | 162,617 |
| Darcy friction factor | 0.018218 |
| Friction loss | 1.0587 bar |
| Elevation loss | 0.97890 bar |
| Pump discharge pressure | 7.0376 bar |
Open this example in the calculator and change any input.
Formula
\(\Delta p_f = f\frac LD\frac{\rho v^2}{2}, \quad p_p = p_n + \Delta p_f + \rho g\Delta z\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | Flow | m³/s |
| \(D\) | Hose inside diameter | m |
| \(L\) | Hose length | m |
| \(\varepsilon\) | Lining roughness | m |
| \(\Delta z\) | Nozzle height above the pump | m |
| \(p_n\) | Nozzle pressure required | Pa |
| \(v\) | Velocity | m/s |
| \(Re\) | Reynolds number | - |
| \(f\) | Darcy friction factor | - |
| \(\Delta p_f\) | Friction loss | Pa |
| \(\Delta p_z\) | Elevation loss | Pa |
| \(p_p\) | Pump discharge pressure | Pa |
Method and standards
Hose loss.
Where it is used
- Fire ground pump pressure.
- Hose layout and relay planning.
Common mistakes
- Using nominal instead of actual inside diameter.
- Ignoring elevation.
Assumptions and limits
- Water at 20 °C; straight hose; no fittings.
References
- Darcy–Weisbach with Colebrook
Questions and answers
Why does doubling the flow quadruple the loss?
Friction loss goes with velocity squared in turbulent flow.
How rough is a hose lining?
Rubber or polyurethane linings are smooth (about 0.01–0.05 mm); the factor is close to smooth-pipe values.
What do the defaults represent?
An illustrative 65 mm hose, 120 m long, flowing 500 L/min to a nozzle 10 m above the pump needing 5 bar.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
White, Fluid Mechanics, 7th ed. (McGraw-Hill, 2011)