FireCADCalc

Fire Hose Friction Loss and Pump Pressure

Friction loss in a fire hose by Darcy–Weisbach with the Colebrook factor, the elevation loss and the pump discharge pressure needed for a nozzle pressure.

Inputs

Examples: Illustrative 65 mm line, 500 L/min45 mm attack line, 250 L/min150 mm supply relay, downhill

Accepted: 0.6 to 60,000 L/min
Accepted: 10 to 200 mm
Accepted: 1 to 5,000 m
Accepted: 0 to 1 mm
Accepted: -500 to 500 m
Accepted: 0 to 20 bar

Results

Hose flow is fully turbulent, so the Darcy–Weisbach loss f(L/D)ρv²/2 with the Colebrook friction factor applies; water at 20 °C is assumed. Loss rises with the square of flow and roughly the fifth power of diameter, which is why large-diameter supply lines feed long relays. The pump must supply nozzle pressure plus friction plus elevation (about 0.1 bar per metre). Fire service rules of thumb (FL = C·Q²·L) are this law with fitted coefficients; couplings, appliances and kinks add further loss.

Velocity2.5113m/s
Reynolds number162,617
Darcy friction factor0.018218
Friction loss1.0587bar
Elevation loss0.97890bar
Pump discharge pressure7.0376bar

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 65 mm line, 500 L/min. The inputs, in the units selected above:

InputValue
Flow500.00 L/min
Hose inside diameter65.000 mm
Hose length120.00 m
Lining roughness0.020000 mm
Nozzle height above the pump10.000 m
Nozzle pressure required5.0000 bar

Applying the formula below gives:

ResultValue
Velocity2.5113 m/s
Reynolds number162,617
Darcy friction factor0.018218
Friction loss1.0587 bar
Elevation loss0.97890 bar
Pump discharge pressure7.0376 bar

Open this example in the calculator and change any input.

Formula

\(\Delta p_f = f\frac LD\frac{\rho v^2}{2}, \quad p_p = p_n + \Delta p_f + \rho g\Delta z\)

Variables

Symbol Meaning SI unit
\(Q\) Flow m³/s
\(D\) Hose inside diameter m
\(L\) Hose length m
\(\varepsilon\) Lining roughness m
\(\Delta z\) Nozzle height above the pump m
\(p_n\) Nozzle pressure required Pa
\(v\) Velocity m/s
\(Re\) Reynolds number -
\(f\) Darcy friction factor -
\(\Delta p_f\) Friction loss Pa
\(\Delta p_z\) Elevation loss Pa
\(p_p\) Pump discharge pressure Pa

Method and standards

Hose loss.

Where it is used

  • Fire ground pump pressure.
  • Hose layout and relay planning.

Common mistakes

  • Using nominal instead of actual inside diameter.
  • Ignoring elevation.

Assumptions and limits

  • Water at 20 °C; straight hose; no fittings.

References

  • Darcy–Weisbach with Colebrook

Questions and answers

Why does doubling the flow quadruple the loss?

Friction loss goes with velocity squared in turbulent flow.

How rough is a hose lining?

Rubber or polyurethane linings are smooth (about 0.01–0.05 mm); the factor is close to smooth-pipe values.

What do the defaults represent?

An illustrative 65 mm hose, 120 m long, flowing 500 L/min to a nozzle 10 m above the pump needing 5 bar.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

White, Fluid Mechanics, 7th ed. (McGraw-Hill, 2011)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.