Worked example
Example: Illustrative water slug 15 m/s, 90 deg, 150 mm. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Slug density | 1,000.0 kg/m³ |
| Slug velocity | 15.000 m/s |
| Pipe inside diameter | 150.00 mm |
| Bend angle | 90.000 ° |
| Dynamic load factor | 2.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Pipe flow area | 176.71 cm² |
| Resultant momentum force | 5.6230 kN |
| Design force with load factor | 11.246 kN |
Open this example in the calculator and change any input.
Formula
\(F = \rho v^2A\sqrt{2(1 - \cos\theta)}, \quad F_d = DLF\cdot F\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\rho\) | Slug density | kg/m³ |
| \(v\) | Slug velocity | m/s |
| \(D\) | Pipe inside diameter | m |
| \(\theta\) | Bend angle | rad |
| \(DLF\) | Dynamic load factor | - |
| \(A\) | Pipe flow area | m² |
| \(F\) | Resultant momentum force | N |
| \(F_d\) | Design force with load factor | N |
Method and standards
Slug momentum.
Where it is used
- Steam and two-phase line supports.
- Gas-condensate pipeline design.
Common mistakes
- Using mixture velocity instead of slug velocity.
- Ignoring the dynamic load factor.
Assumptions and limits
- Slug fills the pipe; incompressible liquid; steady turning.
References
- Momentum balance on a bend
Questions and answers
Where do slugs come from?
Condensate in steam lines, liquid collecting in gas lines, and start-up of two-phase lines; they travel near the gas velocity.
How do I reduce slug loads?
Drain low points, slope lines, warm up slowly and add supports or restraints at elbows.
What do the defaults represent?
An illustrative water slug moving at 15 m/s through a 90° elbow in a 150 mm line, dynamic load factor 2.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Nayyar, Piping Handbook, 7th ed. (McGraw-Hill, 2000)