Worked example
Example: Illustrative 10 kg/s steam from 100 mm. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Fluid at exit | Gas (ideal gas at exit) |
| Mass flow | 36,000 kg/h |
| Exit inside diameter | 100.00 mm |
| Static pressure at exit (absolute) | 4.8000 bar |
| Ambient pressure | 101.33 kPa |
| Gas temperature at exit | 126.85 °C |
| Gas molar mass | 18.015 kg/kmol |
| Liquid density | 1,000.0 kg/m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Exit density | 2.6000 kg/m³ |
| Exit velocity | 489.70 m/s |
| Momentum term | 4.8970 kN |
| Pressure term | 2.9741 kN |
| Reaction force | 7.8711 kN |
Open this example in the calculator and change any input.
Formula
\(F = \dot mv_e + (p_e - p_a)A_e, \quad v_e = \frac{\dot m}{\rho_eA_e}, \quad \rho_e = \frac{p_eM}{RT_e}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{fluid}\) | Fluid at exit | - |
| \(\dot m\) | Mass flow | kg/s |
| \(D_e\) | Exit inside diameter | m |
| \(p_e\) | Static pressure at exit (absolute) | Pa |
| \(p_a\) | Ambient pressure | Pa |
| \(T_e\) | Gas temperature at exit | K |
| \(M\) | Gas molar mass | kg/kmol |
| \(\rho_l\) | Liquid density | kg/m³ |
| \(\rho_e\) | Exit density | kg/m³ |
| \(v_e\) | Exit velocity | m/s |
| \(\dot mv_e\) | Momentum term | N |
| \((p_e - p_a)A_e\) | Pressure term | N |
| \(F\) | Reaction force | N |
Method and standards
Discharge thrust.
Where it is used
- Safety and relief valve outlet supports.
- Vent and blowdown silencer piping.
Common mistakes
- Ignoring the pressure term for choked gas.
- Using upstream rather than exit conditions.
Assumptions and limits
- Steady discharge; uniform exit flow; ideal gas.
References
- Momentum balance at an open discharge
Questions and answers
Why include the pressure term?
A choked gas jet leaves the pipe above ambient pressure; that pressure acting on the exit area adds to the thrust.
How large are relief valve reaction forces?
From a few kilonewtons for small steam valves to tens of kilonewtons for large boiler safety valves.
What do the defaults represent?
An illustrative 10 kg/s steam discharge leaving a 100 mm pipe choked at 4.8 bar(a) and 400 K.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Nayyar, Piping Handbook, 7th ed. (McGraw-Hill, 2000)