Time for Water in an Insulated Pipe to Freeze

Time for still water in an insulated pipe exposed to sub-zero air to cool to 0 °C and then to freeze a chosen fraction, from pipe size, insulation and wind.

Thermal power plantProcess steam and utilities

Inputs

Examples: Illustrative DN50 with 25 mm insulation at -15 CSmall 15 mm bare pipe in windDN100 50 mm insulation at -25 C

Accepted: 5 to 1,000 mm
Accepted: 6 to 1,100 mm
Accepted: 0 to 300 mm
Accepted: 0.01 to 1 W/(m·K)
Accepted: 2 to 100 W/(m²·K)
Accepted: 1 to 56.85 °C
Accepted: -53.15 to -0.05 °C
Accepted: 1 to 100 %

Results

Lumped water cooling through insulation and outside film (pipe wall and inside film neglected); freezing at 0 °C with latent heat 333.55 kJ/kg. Flowing water, heat tracing or draining prevent freezing; a pipe blocks long before it is fully frozen.

Thermal resistance per metre2.9492
Time to cool to 0 °C3.4550h
Time to freeze the fraction8.9418h
Total time12.397h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative DN50 with 25 mm insulation at -15 C. The inputs, in the units selected above:

InputValue
Pipe inside diameter50.000 mm
Pipe outside diameter60.000 mm
Insulation thickness25.000 mm
Insulation conductivity0.035000 W/(m·K)
Outside heat transfer coefficient15.000 W/(m²·K)
Initial water temperature10.000 °C
Air temperature-15.000 °C
Fraction of water frozen25.000 %

Applying the formula below gives:

ResultValue
Thermal resistance per metre2.9492
Time to cool to 0 °C3.4550 h
Time to freeze the fraction8.9418 h
Total time12.397 h

Open this example in the calculator and change any input.

Formula

\(R' = \frac{\ln(r_2/r_1)}{2\pi\lambda} + \frac{1}{2\pi r_2h_o}, \quad t_c = m'c_pR'\ln\frac{T_0 - T_a}{0 - T_a}, \quad t_f = \frac{fm'L_fR'}{0 - T_a}\)

Variables

Symbol Meaning SI unit
\(D_i\) Pipe inside diameter m
\(D_o\) Pipe outside diameter m
\(t_{ins}\) Insulation thickness m
\(\lambda\) Insulation conductivity W/(m·K)
\(h_o\) Outside heat transfer coefficient W/(m²·K)
\(T_0\) Initial water temperature K
\(T_a\) Air temperature K
\(f\) Fraction of water frozen -
\(R'\) Thermal resistance per metre -
\(t_c\) Time to cool to 0 °C s
\(t_f\) Time to freeze the fraction s
\(t\) Total time s

Method and standards

Freeze time.

Where it is used

  • Frost protection of outdoor pipes and fire mains.
  • Deciding on heat tracing or draining.

Common mistakes

  • Assuming insulation prevents freezing.
  • Ignoring wind on exposed pipes.

Assumptions and limits

  • Still water; uniform water temperature.

References

  • Lumped cooling and freezing of water in a pipe

Questions and answers

Does insulation stop a pipe freezing?

No, it only delays it; still water in an insulated pipe will freeze if the cold lasts long enough.

Why do small pipes freeze first?

They hold little water per metre relative to their surface, so they lose their heat and latent store fastest.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Incropera and DeWitt, Fundamentals of Heat and Mass Transfer (Wiley)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.