Hot and Cold Water Mixing: Flows for a Target Temperature

Hot and cold water flows needed to deliver a mixed flow at a target temperature, the hot water share and the heat the heater must supply to make the hot water.

Inputs

Examples: Illustrative shower 12 L/min at 40 CBasin 6 L/min at 38 C, cold winter supplyProcess wash 40 L/min at 50 C

Accepted: 0.06 to 600,000 L/min
Accepted: 1.85 to 96.85 °C
Accepted: 6.85 to 99.85 °C
Accepted: 0 to 66.85 °C

Results

An energy balance on the mixing valve, with constant specific heat and density, gives the hot share x = (T_m − T_c)/(T_h − T_c). The heater must raise that hot flow from the cold supply temperature: P = ρc_pV̇_h(T_h − T_c), with ρ ≈ 992 kg/m³ and c_p ≈ 4.18 kJ/kg·K. Showers use about 38–41 °C; thermostatic mixing valves deliver it safely from stored water at 60 °C or more, which is needed against Legionella.

Hot water share55.556%
Hot water flow6.6667L/min
Cold water flow5.3333L/min
Heater power to make the hot water from cold20.733kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative shower 12 L/min at 40 C. The inputs, in the units selected above:

InputValue
Mixed flow required12.000 L/min
Target mixed temperature40.000 °C
Hot water temperature60.000 °C
Cold water temperature15.000 °C

Applying the formula below gives:

ResultValue
Hot water share55.556 %
Hot water flow6.6667 L/min
Cold water flow5.3333 L/min
Heater power to make the hot water from cold20.733 kW

Open this example in the calculator and change any input.

Formula

\(x_h = \frac{T_m - T_c}{T_h - T_c}, \quad P_h = \rho c_p\dot V_h(T_h - T_c)\)

Variables

Symbol Meaning SI unit
\(\dot V\) Mixed flow required m³/s
\(T_m\) Target mixed temperature K
\(T_h\) Hot water temperature K
\(T_c\) Cold water temperature K
\(x_h\) Hot water share -
\(\dot V_h\) Hot water flow m³/s
\(\dot V_c\) Cold water flow m³/s
\(P_h\) Heater power to make the hot water from cold W

Method and standards

Water mixing.

Where it is used

  • Sizing water heaters for showers and process use.
  • Setting thermostatic mixing valves.

Common mistakes

  • Mixing by volume with very different temperatures without noting density.
  • Forgetting the cold inlet temperature changes with season.

Assumptions and limits

  • Constant properties; adiabatic mixing.

References

  • Mixing energy balance

Questions and answers

Why store water hotter than it is used?

Storage at 60 °C controls Legionella, and mixing makes the stored volume go further.

Does density change matter?

Only slightly; the result is within about 1 % using a constant density.

What do the defaults represent?

An illustrative shower using 12 L/min at 40 °C from 60 °C hot and 15 °C cold water.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

McQuiston, Parker, Spitler and Taherian, Heating, Ventilating and Air Conditioning, and ASHRAE, Principles of Heating, Ventilating and Air Conditioning, 8th ed. (ASHRAE, 2017)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.