FireCADCalc

Hot Water Recirculation Flow for Pipe Heat Loss

Recirculation flow needed to keep a domestic hot water loop within an allowed temperature drop, from pipe length, heat loss per metre and water temperature.

Inputs

Examples: Illustrative 180 m loopHotel loop 600 mSmall house loop

Accepted: 1 to 100,000 m
Accepted: 0.01 to 10 W/(m·K)
Accepted: 26.85 to 96.85 °C
Accepted: -23.15 to 46.85 °C
Accepted: 0.5 to 30 K
Accepted: 5 to 300 mm

Results

A recirculation loop keeps hot water close to the taps by circulating just enough flow to replace the heat the pipes lose: ṁ = Q/(c_pΔT), with Q = U′L(T_w − T_a) and U′ the heat loss per metre per kelvin of the insulated pipe. Water properties are taken near 60 °C (c_p = 4.186 kJ/kg·K, ρ = 983 kg/m³). Keeping the return above about 55 °C limits Legionella growth; velocities above about 0.5–1 m/s in copper risk erosion.

Loop heat loss1,800.0W
Recirculation mass flow309.60kg/h
Recirculation volume flow5.2493L/min
Velocity in the return pipe0.27848m/s

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 180 m loop. The inputs, in the units selected above:

InputValue
Length of the circulation loop (flow pipes)180.00 m
Pipe heat loss coefficient per metre0.25000 W/(m·K)
Hot water temperature60.000 °C
Surrounding air temperature20.000 °C
Allowed temperature drop round the loop5.0000 K
Return pipe inner diameter20.000 mm

Applying the formula below gives:

ResultValue
Loop heat loss1,800.0 W
Recirculation mass flow309.60 kg/h
Recirculation volume flow5.2493 L/min
Velocity in the return pipe0.27848 m/s

Open this example in the calculator and change any input.

Formula

\(\dot Q = U'L(T_w - T_a), \quad \dot m = \frac{\dot Q}{c_p\Delta T}\)

Variables

Symbol Meaning SI unit
\(L\) Length of the circulation loop (flow pipes) m
\(U'\) Pipe heat loss coefficient per metre W/(m·K)
\(T_w\) Hot water temperature K
\(T_a\) Surrounding air temperature K
\(\Delta T\) Allowed temperature drop round the loop K
\(d\) Return pipe inner diameter m
\(\dot Q\) Loop heat loss W
\(\dot m\) Recirculation mass flow kg/s
\(\dot V\) Recirculation volume flow m³/s
\(v\) Velocity in the return pipe m/s

Method and standards

Recirculation flow.

Where it is used

  • Sizing hot water circulation pumps.
  • Hotels, hospitals and large residential buildings.

Common mistakes

  • Including branches that are not circulated.
  • Ignoring the heat loss of the return pipe itself (include it in L).

Assumptions and limits

  • Steady state; uniform insulation; water near 60 °C.

References

  • Heat balance of a recirculation loop

Questions and answers

What temperature drop is allowed?

Usually about 5 K, so a loop leaving at 60 °C returns above 55 °C.

Where does the heat loss per metre come from?

From the insulation calculation or manufacturer's data for the pipe and insulation thickness.

What do the defaults represent?

An illustrative 180 m loop of insulated pipe losing 0.25 W/m·K at 60 °C in 20 °C surroundings, 5 K drop, 20 mm return.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

McQuiston, Parker, Spitler and Taherian, Heating, Ventilating and Air Conditioning, and ASHRAE, Principles of Heating, Ventilating and Air Conditioning, 8th ed. (ASHRAE, 2017)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.