FireCADCalc

Low Chilled-Water ΔT: Extra Flow and Pump Energy

Extra chilled-water flow and pumping energy when the coil temperature difference falls below design, for the same cooling load, with the annual cost.

Thermal power plantProcess steam and utilities

Inputs

Examples: Illustrative 2 MW, 6 K design at 4 KLarge plant 8 K design at 5 KMild 5.5 to 5 K

Accepted: 1 to 100,000 kW
Accepted: 1 to 20 K
Accepted: 0.5 to 20 K
Accepted: 0.1 to 10,000 kW
Accepted: 1 to 3
Accepted: 0 to 8,760 h
Accepted: 0 to 100

Results

Same load at a lower ΔT needs proportionally more flow (water at 10 °C from IAPWS-IF97); pump power rises roughly with flow to the power n. Low ΔT also forces extra chillers on line; common causes are open bypasses, three-way valves, dirty coils and low supply set-points.

Design flow286.13m³/h
Actual flow429.20m³/h
Flow increase50.000%
Pump power at actual flow82.670kW
Extra pump energy per year158.01MWh
Extra cost per year18,961

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 2 MW, 6 K design at 4 K. The inputs, in the units selected above:

InputValue
Cooling load2,000.0 kW
Design temperature difference6.0000 K
Actual temperature difference4.0000 K
Pump power at design flow30.000 kW
Pump power exponent on flow (3 ideal, 2–2.5 with fixed head)2.5000 -
Hours per year at this condition3,000.0 h
Electricity price per kWh0.12000 -

Applying the formula below gives:

ResultValue
Design flow286.13 m³/h
Actual flow429.20 m³/h
Flow increase50.000 %
Pump power at actual flow82.670 kW
Extra pump energy per year158.01 MWh
Extra cost per year18,961

Open this example in the calculator and change any input.

Formula

\(\dot V = \frac{\dot Q}{\rho c_p\Delta T}, \quad P_a = P_d\left(\frac{\dot V_a}{\dot V_d}\right)^n\)

Variables

Symbol Meaning SI unit
\(\dot Q\) Cooling load W
\(\Delta T_d\) Design temperature difference K
\(\Delta T_a\) Actual temperature difference K
\(P_d\) Pump power at design flow W
\(n\) Pump power exponent on flow (3 ideal, 2–2.5 with fixed head) -
\(t\) Hours per year at this condition s
\(c_e\) Electricity price per kWh -
\(\dot V_d\) Design flow m³/s
\(\dot V_a\) Actual flow m³/s
\(\Delta\dot V\) Flow increase -
\(P_a\) Pump power at actual flow W
\(\Delta E\) Extra pump energy per year J
\(\Delta C\) Extra cost per year -

Method and standards

ΔT penalty.

Where it is used

  • Chiller plant audits.
  • Justifying two-way valves and coil cleaning.

Common mistakes

  • Blaming chillers for a coil-side problem.
  • Using the ideal cube law with large fixed head.

Assumptions and limits

  • Constant load; water properties at 10 °C.

References

  • Sensible heat balance of the chilled-water loop with pump affinity
  • ASHRAE Handbook of Fundamentals (ASHRAE)

Questions and answers

What is low ΔT syndrome?

Return water comes back colder than designed, so the plant must pump more water and run more chillers to meet the same load.

How much does it cost?

Dropping from 6 K to 4 K raises flow by 50 % and pump power by roughly 1.8 to 3.4 times, depending on the system curve.

What do the defaults represent?

An illustrative 2 MW plant designed for 6 K running at 4 K, 30 kW pumps at design flow, 3,000 hours a year at 0.12 per kWh.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.