Worked example
Example: Illustrative hotel, 2,000 L/day. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Hot water per day | 2,000.0 L |
| Cold water temperature | 20.000 °C |
| Hot water temperature | 60.000 °C |
| Heat pump seasonal COP | 3.5000 - |
| Electric heater efficiency (including standing loss) | 90.000 % |
| Days per year | 365.00 - |
| Electricity price per kWh | 8.0000 - |
| Extra cost of the heat pump | 300,000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Heat per day | 91.774 kWh |
| Heat pump electricity per day | 26.221 kWh |
| Electric heater electricity per day | 101.97 kWh |
| Saving per year | 221,190 |
| Payback (years) | 1.3563 |
Open this example in the calculator and change any input.
Formula
\(Q = \rho V c_p (T_o - T_i), \quad E_{hp} = \frac{Q}{COP}, \quad E_e = \frac{Q}{\eta_e}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V\) | Hot water per day | m³ |
| \(T_i\) | Cold water temperature | K |
| \(T_o\) | Hot water temperature | K |
| \(COP\) | Heat pump seasonal COP | - |
| \(\eta_e\) | Electric heater efficiency (including standing loss) | - |
| \(d\) | Days per year | - |
| \(c\) | Electricity price per kWh | - |
| \(C_x\) | Extra cost of the heat pump | - |
| \(Q_d\) | Heat per day | J |
| \(E_{hp}\) | Heat pump electricity per day | J |
| \(E_e\) | Electric heater electricity per day | J |
| \(\Delta C\) | Saving per year | - |
| \(t_{pb}\) | Payback (years) | - |
Method and standards
Heat pump water heater.
Where it is used
- Hotels, hospitals, hostels and homes.
- Replacing electric or fuel water heaters.
Common mistakes
- Using the rated COP at high ambient for the whole year.
- Ignoring standby losses of the electric heater.
Assumptions and limits
- Water density at about 50 °C; seasonal COP.
References
- Heating energy and COP comparison
Questions and answers
How much does a heat pump save on 2,000 L/day of 60 °C water?
About 92 kWh of heat a day: about 26 kWh with the heat pump against 102 kWh electric, near 2.2 lakh a year at 8 per kWh.
Does COP fall in winter?
Yes, colder air lowers COP; use a seasonal value for your climate.
What do the defaults represent?
An illustrative hotel heating 2,000 L/day from 20 °C to 60 °C, heat pump COP 3.5 against a 90 % electric heater, all year at 8 per kWh.