Electric Heat Tracing for Pipe Freeze Protection

Heat loss of an insulated pipe at the lowest ambient for a maintain temperature, the design heat with margin, number of tracer passes and circuit power.

Thermal power plantProcess steam and utilitiesRefinery and petrochemical

Inputs

Examples: Illustrative DN100, 50 mm insulation, 5 C at -20 CDN50 at -30 C, 30 mm insulationFuel oil DN150 kept at 60 C

Accepted: 10 to 1,500 mm
Accepted: 5 to 300 mm
Accepted: 0.01 to 0.5 W/(m·K)
Accepted: 2 to 100 W/(m²·K)
Accepted: 0 to 226.85 °C
Accepted: -53.15 to 26.85 °C
Accepted: 1 to 2
Accepted: 5 to 200 W/m
Accepted: 1 to 2,000 m
Accepted: 100 to 700 V

Results

q' = (T_m − T_a)/R', R' = ln(r₂/r₁)/(2πλ) + 1/(2πr₂h); add valves, flanges and supports as extra length (often 10–30 %). Self-regulating cable output falls as pipe temperature rises; take output and maximum circuit length from the maker's data.

Heat loss per metre12.108W/m
Design heat per metre14.530W/m
Tracer passes1.0000
Circuit power0.90000kW
Circuit current3.9130A

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative DN100, 50 mm insulation, 5 C at -20 C. The inputs, in the units selected above:

InputValue
Pipe outside diameter114.00 mm
Insulation thickness50.000 mm
Insulation conductivity at mean temperature0.040000 W/(m·K)
Outside heat transfer coefficient15.000 W/(m²·K)
Maintain temperature5.0000 °C
Lowest ambient temperature-20.000 °C
Safety factor1.2000 -
Cable output at the maintain temperature25.000 W/m
Circuit length100.00 m
Supply voltage230.00 V

Applying the formula below gives:

ResultValue
Heat loss per metre9.5970 W/m
Design heat per metre11.516 W/m
Tracer passes1.0000
Circuit power2.5000 kW
Circuit current10.870 A

Open this example in the calculator and change any input.

Formula

\(q' = \frac{T_m - T_a}{\frac{\ln(r_2/r_1)}{2\pi\lambda} + \frac{1}{2\pi r_2h_o}}, \quad n = \left\lceil\frac{k_sq'}{q_c}\right\rceil\)

Variables

Symbol Meaning SI unit
\(D_o\) Pipe outside diameter m
\(t_{ins}\) Insulation thickness m
\(\lambda\) Insulation conductivity at mean temperature W/(m·K)
\(h_o\) Outside heat transfer coefficient W/(m²·K)
\(T_m\) Maintain temperature K
\(T_a\) Lowest ambient temperature K
\(k_s\) Safety factor -
\(q_c\) Cable output at the maintain temperature W/m
\(L\) Circuit length m
\(V\) Supply voltage V
\(q'\) Heat loss per metre W/m
\(q'_d\) Design heat per metre W/m
\(n\) Tracer passes -
\(P\) Circuit power W
\(I\) Circuit current A

Method and standards

Trace heating.

Where it is used

  • Freeze protection of water, fire and process lines.
  • Temperature maintenance of viscous products.

Common mistakes

  • Forgetting heat sinks at valves and supports.
  • Using cable output at a lower temperature than maintained.

Assumptions and limits

  • Steady state; dry insulation.

References

  • Cylindrical insulation heat loss for trace heating

Questions and answers

How much heat does freeze protection need?

Typically 10–30 W/m for small insulated pipes in cold climates; process temperature maintenance needs more.

Why a safety factor?

Insulation gets wet or damaged and real conductivities exceed catalogue values.

What do the defaults represent?

An illustrative DN100 pipe with 50 mm insulation kept at 5 °C at −20 °C ambient, 25 W/m cable, 100 m circuit at 230 V.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Nayyar, Piping Handbook, 7th ed. (McGraw-Hill, 2000)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.