Sprinkler and Nozzle K-Factor Flow Q = K√P

Flow from a fire sprinkler, spray nozzle or water mist head at a pressure, or the pressure needed for a flow, from its K-factor, in metric and US units.

Process steam and utilitiesRefinery and petrochemicalChemical and fertiliserPump

Inputs

Examples: K 80 at 1 barK 115 for 200 L/minK 80.7 at 0.5 bar

From the sprinkler or nozzle data sheet. A K given in US gpm/psi^½ times 14.42 gives L/min/bar^½.

Results

Minimum pressures, densities and design areas come from the fire code (NFPA 13, EN 12845 or your local rules) and the listing of the sprinkler.

Flow200.00L/min
Pressure3.0246bar
K-factor in US gpm per psi^½7.9771

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: K 80 at 1 bar. The inputs, in the units selected above:

InputValue
FindFlow at a pressure
K-factor, L/min per bar^½80.000 -
Pressure at the sprinkler or nozzle1.0000 bar
Flow wanted80.000 L/min

Applying the formula below gives:

ResultValue
Flow80.000 L/min
Pressure1.0000 bar
K-factor in US gpm per psi^½5.5493

Open this example in the calculator and change any input.

Formula

\(Q = K \sqrt{P}\ \ (\text{L/min, bar}), \quad P = \left(\frac{Q}{K}\right)^2\)

\(K = 14.42\, K_{US}\)

Variables

Symbol Meaning SI unit
\(\text{find}\) Find -
\(K\) K-factor, L/min per bar½ -
\(P\) Pressure at the sprinkler or nozzle Pa
\(Q\) Flow wanted m³/s
\(K_{US}\) K-factor in US gpm per psi½ -

Method and standards

A sprinkler or nozzle behaves as an orifice; its K-factor lumps the area and discharge coefficient. The conversion factor follows from the exact definitions of the US gallon and psi.

Where it is used

  • Hydraulic calculation of sprinkler and deluge systems.
  • Spray nozzle selection for cooling and scrubbing.
  • Checking a nozzle's flow on site from a pressure gauge.

Common mistakes

  • Mixing metric and US K-factors.
  • Using the supply pressure instead of the pressure at the head.
  • Forgetting minimum operating pressures in the fire code.

Assumptions and limits

  • Water at ordinary temperature.
  • K-factor from the listing or data sheet.

References

  • Orifice discharge Q = K√P (NFPA 13 and EN 12845 K-factor convention)

Questions and answers

How much water does a K80 sprinkler give at 1 bar?

80 L/min. At 0.5 bar it gives 57 L/min: flow goes with the square root of pressure.

What pressure does K115 need for 200 L/min?

(200/115)² = 3.0 bar at the sprinkler.

How do I convert a US K-factor?

Multiply gpm/psi½ by 14.42 to get L/min/bar½: K5.6 is about K80.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.