Worked example
Example: Duct 400 × 200 mm. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Cross-section | Rectangle a × b, full |
| Width a, outer diameter D | 400.00 mm |
| Height b, inner diameter d, or depth h | 200.00 mm |
Applying the formula below gives:
| Result | Value |
|---|---|
| Flow area | 0.080000 m² |
| Wetted perimeter | 1.2000 m |
| Hydraulic diameter 4A/P | 266.67 mm |
Open this example in the calculator and change any input.
Formula
\(D_h = \frac{4A}{P_w}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{shape}\) | Cross-section | - |
| \(a\) | Width a, outer diameter D | m |
| \(b\) | Height b, inner diameter d, or depth h | m |
| \(A\) | Flow area | m² |
| \(P_w\) | Wetted perimeter | m |
| \(D_h\) | Hydraulic diameter 4A/P | m |
Method and standards
Definition.
Where it is used
- Non-circular ducts and annuli.
- Heat exchanger shells and channels.
Common mistakes
- Using D_h for the flow area.
- Including the free surface.
Assumptions and limits
- Uniform cross-section.
References
- D_h = 4A/P (Textbook fluid mechanics (White, Fluid Mechanics))
Questions and answers
A 400 × 200 mm duct?
D_h = 4 × 0.08 / 1.2 = 267 mm.
An annulus?
D − d.
Is it the same as the equivalent diameter for duct sizing?
No: the duct-sizing equivalent diameter keeps the same pressure drop for the same flow; D_h is for Reynolds number and friction.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.