Worked example
Example: 10 000 m3/d, MLSS 3500. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Average influent flow | 10,000 m³/d |
| Peak flow factor | 2.5000 - |
| Return sludge ratio | 0.50000 - |
| MLSS | 3,500.0 mg/L |
| Maximum surface overflow rate at peak | 1.6667 m/h |
| Maximum solids loading rate at peak | 9.0000 kg/(m²·h) |
| Number of clarifiers | 2.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Area by overflow rate | 625.00 m² |
| Area by solids loading | 486.11 m² |
| Governing area | 625.00 m² |
| Diameter of each clarifier | 19.947 m |
| Overflow rate at average flow | 0.66667 m/h |
| Solids loading at average flow | 3.5000 kg/(m²·h) |
Open this example in the calculator and change any input.
Formula
\(A_{SOR} = \frac{Q_p}{SOR_{max}}, \quad A_{SLR} = \frac{(Q_p + RQ)X}{SLR_{max}}, \quad A = \max(A_{SOR}, A_{SLR})\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | Average influent flow | m³/s |
| \(PF\) | Peak flow factor | - |
| \(R\) | Return sludge ratio | - |
| \(X\) | MLSS | kg/m³ |
| \(SOR_{max}\) | Maximum surface overflow rate at peak | m/s |
| \(SLR_{max}\) | Maximum solids loading rate at peak | kg/(m²·s) |
| \(n\) | Number of clarifiers | - |
| \(A_{SOR}\) | Area by overflow rate | m² |
| \(A_{SLR}\) | Area by solids loading | m² |
| \(A\) | Governing area | m² |
| \(D\) | Diameter of each clarifier | m |
| \(SOR_{avg}\) | Overflow rate at average flow | m/s |
| \(SLR_{avg}\) | Solids loading at average flow | kg/(m²·s) |
Method and standards
Overflow and solids loading definitions.
Where it is used
- Activated sludge plant design.
- Checking clarifiers before raising MLSS.
Common mistakes
- Using average flow only.
- Ignoring return sludge in the solids loading.
Assumptions and limits
- Circular clarifiers of equal size; the number of clarifiers is a whole number (a fractional entry is rounded, with a note).
References
- Metcalf & Eddy
- Wastewater Engineering: Treatment and Resource Recovery
- 5th ed. (McGraw-Hill, 2014)
- ch. 8 (secondary clarifier overflow and solids loading rates)
Questions and answers
Which limit usually governs?
Solids loading at peak flow for plants with high MLSS; overflow rate for low MLSS or high peak factors.
Why include return flow in solids loading?
The clarifier carries influent plus return sludge downward; both bring solids to the sludge blanket.
What do the defaults give?
10,000 m³/d, peak 2.5, MLSS 3,500 mg/L: overflow rate governs: about 625 m² in total, two clarifiers of about 20 m.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.