FireCADCalc

Nitrification: Oxygen, Alkalinity and Chemical Make-Up

Oxygen used and alkalinity destroyed by nitrifying ammonia (4.57 g O₂ and 7.14 g CaCO₃ per g N), the alkalinity left, and the lime or soda needed to keep a minimum.

Sugar mill and cogenerationDistillery and ethanolRefinery and petrochemicalChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 10 000 m3/d, 30 mg/L NH4-N, alk 200With 20 mg/L denitrified

Results

Alkalinity remaining is negative: the influent cannot supply this much nitrification; pH would fall and nitrification stall before this point. The chemical dose shown restores the minimum.

Chemical doses are for 100 % pure Ca(OH)₂ or NaHCO₃: divide by the purity of the product used.

Stoichiometric values for complete nitrification; cell synthesis lowers them slightly (Metcalf & Eddy quote 4.25 g O₂ and 7.07 g CaCO₃ per g N with growth). Keep 50–80 mg/L alkalinity for stable nitrification.

Oxygen for nitrification1,371.0kg/d
Alkalinity consumed (as CaCO₃)214.20mg/L
Alkalinity remaining-14.200mg/L
Hydrated lime Ca(OH)₂ to add623.32kg/d
Or sodium bicarbonate to add1,413.4kg/d

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 10 000 m3/d, 30 mg/L NH4-N, alk 200. The inputs, in the units selected above:

InputValue
Flow10,000 m³/d
Ammonia nitrogen nitrified30.000 mg/L
Influent alkalinity (as CaCO₃)200.00 mg/L
Alkalinity to keep (as CaCO₃)70.000 mg/L
Nitrate denitrified (returns alkalinity)0 mg/L

Applying the formula below gives:

ResultValue
Oxygen for nitrification1,371.0 kg/d
Alkalinity consumed (as CaCO₃)214.20 mg/L
Alkalinity remaining-14.200 mg/L
Hydrated lime Ca(OH)₂ to add623.32 kg/d
Or sodium bicarbonate to add1,413.4 kg/d

Open this example in the calculator and change any input.

Formula

\(O_2 = 4.57\,\Delta N\,Q, \quad Alk_c = 7.14\,\Delta NH_4\text{-}N - 3.57\,\Delta NO_3\text{-}N, \quad m_{Ca(OH)_2} = (Alk_{min} - Alk_r)Q\frac{74.09}{100.09}\)

Variables

Symbol Meaning SI unit
\(Q\) Flow m³/s
\(\Delta NH_4\text{-}N\) Ammonia nitrogen nitrified kg/m³
\(Alk\) Influent alkalinity (as CaCO₃) kg/m³
\(Alk_{min}\) Alkalinity to keep (as CaCO₃) kg/m³
\(\Delta NO_3\text{-}N\) Nitrate denitrified (returns alkalinity) kg/m³
\(\dot m_{O_2}\) Oxygen for nitrification kg/s
\(Alk_c\) Alkalinity consumed (as CaCO₃) kg/m³
\(Alk_r\) Alkalinity remaining kg/m³
\(\dot m_{lime}\) Hydrated lime Ca(OH)₂ to add kg/s
\(\dot m_{NaHCO_3}\) Or sodium bicarbonate to add kg/s

Method and standards

Stoichiometry.

Where it is used

  • Activated sludge with nitrification.
  • Ammonia-rich industrial effluents.

Common mistakes

  • Forgetting alkalinity on low-alkalinity waters.
  • Counting denitrification that does not happen.

Assumptions and limits

  • Complete nitrification.
  • Lime and sodium bicarbonate doses are for 100 % pure chemicals; divide by the product purity.

References

  • Metcalf & Eddy
  • Wastewater Engineering: Treatment and Resource Recovery
  • 5th ed. (McGraw-Hill, 2014)
  • ch. 7 (nitrification stoichiometry: 4.57 g O₂ and 7.14 g CaCO₃ per g NH₄-N; denitrification returns 3.57 g CaCO₃ per g NO₃-N)

Questions and answers

Why does nitrification use alkalinity?

Oxidising ammonium to nitrate releases hydrogen ions; without enough alkalinity pH falls and nitrifiers stop working.

How does denitrification help?

Reducing nitrate back to nitrogen gas returns about half the alkalinity, 3.57 g per g N.

What do the defaults give?

10,000 m³/d nitrifying 30 mg/L: 1,370 kg/d of oxygen, 214 mg/L alkalinity used, so about 620 kg/d of lime to keep 70 mg/L.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.