FireCADCalc

Coagulant and Chemical Solution Feed Rate

Chemical consumption and dosing pump flow for a coagulant or other chemical from the dose, water flow, product strength and solution density.

Refinery and petrochemicalChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: Alum 30 mg/L, 10 % solutionPAC 12 mg/L, 18 % solution

Results

Dose from jar tests; size the pump for the maximum dose and flow.

Product consumption345.60kg/d
Solution feed rate58.824L/h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Alum 30 mg/L, 10 % solution. The inputs, in the units selected above:

InputValue
Dose (as product)30.000 mg/L
Water flow500.00 m³/h
Solution strength (mass fraction of product)10.000 %
Solution density1,050.0 kg/m³

Applying the formula below gives:

ResultValue
Product consumption360.00 kg/d
Solution feed rate142.86 L/h

Open this example in the calculator and change any input.

Formula

\(\dot m = d\,\dot V, \quad \dot V_s = \frac{\dot m}{w\rho}\)

Variables

Symbol Meaning SI unit
\(d\) Dose (as product) kg/m³
\(\dot V\) Water flow m³/s
\(w\) Solution strength (mass fraction of product) -
\(\rho\) Solution density kg/m³
\(\dot m\) Product consumption (shown per day by default) kg/s
\(\dot V_s\) Solution feed rate m³/s

Method and standards

Mass balance.

Where it is used

  • Clarifiers and pre-treatment.
  • Effluent treatment.

Common mistakes

  • Dose as active vs as product.
  • Ignoring solution density.

Assumptions and limits

  • Steady flow.

References

  • Mass balance: product = dose × flow; solution = product/(strength × density)

Questions and answers

30 mg/L on 500 m³/h with 10 % solution?

360 kg/day of product, 143 L/h of solution.

Dose as product or as Al?

State which; doses as Al₂O₃ or Al need conversion.

Pump size?

Cover peak flow × peak dose with turndown for the minimum.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.