Worked example
Example: Alum 30 mg/L, 10 % solution. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Dose (as product) | 30.000 mg/L |
| Water flow | 500.00 m³/h |
| Solution strength (mass fraction of product) | 10.000 % |
| Solution density | 1,050.0 kg/m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Product consumption | 360.00 kg/d |
| Solution feed rate | 142.86 L/h |
Open this example in the calculator and change any input.
Formula
\(\dot m = d\,\dot V, \quad \dot V_s = \frac{\dot m}{w\rho}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(d\) | Dose (as product) | kg/m³ |
| \(\dot V\) | Water flow | m³/s |
| \(w\) | Solution strength (mass fraction of product) | - |
| \(\rho\) | Solution density | kg/m³ |
| \(\dot m\) | Product consumption (shown per day by default) | kg/s |
| \(\dot V_s\) | Solution feed rate | m³/s |
Method and standards
Mass balance.
Where it is used
- Clarifiers and pre-treatment.
- Effluent treatment.
Common mistakes
- Dose as active vs as product.
- Ignoring solution density.
Assumptions and limits
- Steady flow.
References
- Mass balance: product = dose × flow; solution = product/(strength × density)
Questions and answers
30 mg/L on 500 m³/h with 10 % solution?
360 kg/day of product, 143 L/h of solution.
Dose as product or as Al?
State which; doses as Al₂O₃ or Al need conversion.
Pump size?
Cover peak flow × peak dose with turndown for the minimum.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.