Worked example
Example: 1 mg/L, 400 m3, 10 000 m3/d, BF 0.5. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Free chlorine residual at the outlet | 1.0000 mg/L |
| Contact tank volume | 400.00 m³ |
| Peak flow | 10,000 m³/d |
| Baffling factor t₁₀/T | 0.50000 - |
| Required CT (mg·min/L) | 30.000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Theoretical detention time | 57.600 min |
| Effective contact time | 28.800 min |
| CT achieved (mg·min/L) | 28.800 |
| Ratio to the requirement | 0.96000 |
| Tank volume to meet the requirement | 416.67 m³ |
Open this example in the calculator and change any input.
Formula
\(T = \frac{V}{Q}, \quad t_{10} = BF\cdot T, \quad CT = C\,t_{10}, \quad V_{req} = V\frac{CT_{req}}{CT}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(C\) | Free chlorine residual at the outlet | kg/m³ |
| \(V\) | Contact tank volume | m³ |
| \(Q\) | Peak flow | m³/s |
| \(BF\) | Baffling factor t₁₀/T | - |
| \(CT_{req}\) | Required CT (mg·min/L) | - |
| \(T\) | Theoretical detention time | s |
| \(t_{10}\) | Effective contact time | s |
| \(CT\) | CT achieved (mg·min/L) | - |
| \(CT/CT_{req}\) | Ratio to the requirement | - |
| \(V_{req}\) | Tank volume to meet the requirement | m³ |
Method and standards
CT concept.
Where it is used
- Drinking water and effluent disinfection.
- Cooling and process water.
Common mistakes
- Using average instead of peak flow.
- Using the dose instead of the residual.
Assumptions and limits
- Steady flow; residual at the outlet.
References
- US EPA
- Disinfection Profiling and Benchmarking Guidance Manual (EPA 815-R-99-013): CT = C × t₁₀ and baffling factors
Questions and answers
What is t₁₀?
The time by which 10 % of the water has passed through the tank; short-circuiting makes it shorter than V/Q.
Why use the outlet residual?
It is the lowest concentration in the tank, so CT is conservative.
What do the defaults give?
1 mg/L in 400 m³ at 10,000 m³/d, BF 0.5: t₁₀ about 29 min, CT 29: just short of 30.