Worked example
Example: Alum, 5 mg/L P, Al:P 2. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Flow | 10,000 m³/d |
| Phosphorus to remove | 5.0000 mg/L |
| Chemical | Alum Al₂(SO₄)₃·14H₂O |
| Molar metal-to-phosphorus ratio | 2.0000 - |
| Solution strength (mass fraction of the product named above: alum as the 14-hydrate, ferric chloride as FeCl₃) | 48.000 % |
| Solution density | 1,330.0 kg/m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Metal dose (as Al or Fe) | 8.7112 mg/L |
| Dry chemical | 959.51 kg/d |
| Solution volume | 62.625 L/h |
Open this example in the calculator and change any input.
Formula
\(n_M = \frac{\Delta P}{30.974}\cdot(M{:}P), \quad C_M = n_M A_M, \quad \dot m = n_M\,\frac{M_{chem}}{\nu_M}\,Q, \quad \dot V = \frac{\dot m}{w\rho}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | Flow | m³/s |
| \(\Delta P\) | Phosphorus to remove | kg/m³ |
| \(\text{chemical}\) | Chemical | - |
| \(M:P\) | Molar metal-to-phosphorus ratio | - |
| \(w\) | Solution strength (mass fraction) | - |
| \(\rho\) | Solution density | kg/m³ |
| \(C_M\) | Metal dose (as Al or Fe) | kg/m³ |
| \(n_M\) | Metal to add, molar | kmol/m³ |
| \(A_M\) | Atomic mass of the metal | kg/kmol |
| \(M_{chem}/\nu_M\) | Product mass per kmol of metal | kg/kmol |
| \(\dot m\) | Dry chemical | kg/s |
| \(\dot V\) | Solution volume | m³/s |
Method and standards
Stoichiometry.
Where it is used
- Effluent phosphorus limits.
- Dairy and food wastewater.
Common mistakes
- Using the mass ratio instead of the molar ratio.
- Forgetting that alum carries two Al per molecule.
Assumptions and limits
- Molar ratio from jar tests or practice.
- n_M is the metal in kmol per m³; A_M is 26.982 kg/kmol for Al and 55.845 kg/kmol for Fe. M_chem/ν_M is the product mass per mole of metal: 594.4/2 kg/kmol for Al₂(SO₄)₃·14H₂O, 162.2 kg/kmol for FeCl₃.
- Solution strength as the 14-hydrate for alum; a strength quoted as anhydrous Al₂(SO₄)₃ or as Al₂O₃ must be converted first.
References
- Metcalf & Eddy
- Wastewater Engineering: Treatment and Resource Recovery
- 5th ed. (McGraw-Hill, 2014)
- ch. 6 (chemical phosphorus removal, molar ratios)
Questions and answers
Why a molar ratio above 1?
Metal also forms hydroxides and reacts with alkalinity; extra metal is needed to drive phosphorus low.
Alum or ferric?
Both work; ferric also helps sulfide and odour control and sludge thickening, alum gives lighter-coloured sludge.
What do the defaults give?
5 mg/L P at Al:P 2 in 10,000 m³/d: 8.7 mg/L Al, 960 kg/d of alum, about 63 L/h of 48 % solution.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.