Worked example
Example: 5 ppm at 50 t/h. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Water or feedwater flow | 50.000 t/h |
| Dose of active chemical | 5.0000 ppm |
| Active strength of the dosing solution | 5.0000 % |
| Solution density | 1,030.0 kg/m³ |
| Pump capacity at 100 % stroke | 10.000 L/h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Active chemical | 0.25000 kg/h |
| Solution flow | 4.8544 L/h |
| Stroke setting | 48.544 % |
Open this example in the calculator and change any input.
Formula
\(\dot m_a = \dot m_w c, \quad \dot V_s = \frac{\dot m_a}{w\rho_s}, \quad s = \frac{\dot V_s}{\dot V_{max}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_w\) | Water or feedwater flow | kg/s |
| \(c\) | Dose of active chemical | - |
| \(w\) | Active strength of the dosing solution | - |
| \(\rho_s\) | Solution density | kg/m³ |
| \(\dot V_{max}\) | Pump capacity at 100 % stroke | m³/s |
| \(\dot m_a\) | Active chemical | kg/s |
| \(\dot V_s\) | Solution flow | m³/s |
| \(s\) | Stroke setting | - |
Method and standards
Mass balance.
Where it is used
- Dosing system set-up.
Common mistakes
- Dose of product used as active.
Assumptions and limits
- Linear pump. A stroke above 100 % means the pump is too small; a note says so.
References
- Mass balance: active chemical = flow × dose; solution = active/(strength × density)
Questions and answers
Why aim for mid-range stroke?
Metering pumps are least accurate near the ends of their range.
Strength or stroke?
Change the solution strength for large changes; fine-tune with stroke.
Dose as product or active?
This calculator works in active chemical; enter the product's active strength.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.