FireCADCalc

Hydroxide, Carbonate and Bicarbonate from P and M Alkalinity

Splits total alkalinity into hydroxide, carbonate and bicarbonate from the phenolphthalein (P) and methyl orange (M) alkalinity titrations, as CaCO₃.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserBoilerWater treatment plant

Inputs

Examples: Raw water: P 0, M 250 mg/LSoftened boiler water: P 300, M 500 mg/LBoiler water: P 60, M 200 mg/L

Results

The standard relations assume no other buffers (phosphate, silicate, ammonia); in treated boiler water they give an approximation.

Hydroxide alkalinity, as CaCO₃0mg/L
Carbonate alkalinity, as CaCO₃120.00mg/L
Bicarbonate alkalinity, as CaCO₃80.000mg/L

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Raw water: P 0, M 250 mg/L. The inputs, in the units selected above:

InputValue
Phenolphthalein (P) alkalinity, as CaCO₃0 mg/L
Total (M, methyl orange) alkalinity, as CaCO₃250.00 mg/L

Applying the formula below gives:

ResultValue
Hydroxide alkalinity, as CaCO₃0 mg/L
Carbonate alkalinity, as CaCO₃0 mg/L
Bicarbonate alkalinity, as CaCO₃250.00 mg/L

Open this example in the calculator and change any input.

Formula

\(P = 0: HCO_3 = M \qquad 2P < M: CO_3 = 2P,\ HCO_3 = M - 2P \qquad 2P = M: CO_3 = M \qquad 2P > M: OH = 2P - M,\ CO_3 = 2(M - P) \qquad P = M: OH = M\)

Variables

Symbol Meaning SI unit
\(P\) phenolphthalein alkalinity as CaCO₃ kg/m³
\(M\) total (methyl orange) alkalinity as CaCO₃ kg/m³
\(OH\) hydroxide alkalinity kg/m³
\(CO_3\) carbonate alkalinity kg/m³
\(HCO_3\) bicarbonate alkalinity kg/m³

Method and standards

The standard relationships between P and M alkalinity and the hydroxide, carbonate and bicarbonate forms, all as CaCO₃.

Where it is used

  • Boiler water control.
  • Raw and make-up water analysis.
  • Estimating CO₂ release potential.

Common mistakes

  • Applying the relations where phosphate, silicate or ammonia add buffering.
  • Mixing mg/L as ion with mg/L as CaCO₃.
  • Titrating hot samples.

Assumptions and limits

  • Alkalinity from hydroxide, carbonate and bicarbonate only.

References

  • APHA
  • Standard Methods for the Examination of Water and Wastewater
  • method 2320 (alkalinity): relationships of hydroxide
  • carbonate and bicarbonate alkalinity from P and M titrations

Questions and answers

How do I split P and M alkalinity?

If P is zero, all is bicarbonate; if 2P < M, carbonate is 2P and bicarbonate M − 2P; if 2P > M, hydroxide is 2P − M and carbonate 2(M − P); if P = M, all is hydroxide. Boiler water with P 300 and M 500 mg/L has 100 hydroxide and 400 carbonate.

Why does boiler water need hydroxide alkalinity?

A controlled OH alkalinity keeps silica soluble and protects steel; too much causes caustic attack and foaming.

What causes CO₂ in steam?

Bicarbonate and carbonate break down in the boiler, releasing CO₂; dealkalising the make-up reduces it.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.