FireCADCalc

Superheater Steam Mass Flux and Velocity

Steam mass flux and velocity in superheater tubes from the steam flow, number of parallel tubes, bore and the steam state (IF97 density).

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolIAPWS-IF97 (water and steam)Boiler

Inputs

Examples: 67 bar, 430 °CLow pressure SH

Results

Too low a mass flux overheats tubes; too high costs pressure drop. Designs balance the two pass by pass.

The steam velocity, 30.1 m/s, is outside the 10–25 m/s often used for superheaters: check it against your design practice.

Steam density7.7355kg/m³
Mass flux233.16kg/(m²·s)
Steam velocity30.142m/s

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 67 bar, 430 °C. The inputs, in the units selected above:

InputValue
Steam flow60.000 t/h
Parallel tubes48.000 -
Tube bore38.100 mm
Steam pressure (absolute)67.000 bar
Steam temperature430.00 °C

Applying the formula below gives:

ResultValue
Steam density22.408 kg/m³
Mass flux304.56 kg/(m²·s)
Steam velocity13.591 m/s

Open this example in the calculator and change any input.

Formula

\(G = \frac{\dot m_s}{n \pi d_i^2/4}, \quad v = \frac{G}{\rho}\)

Variables

Symbol Meaning SI unit
\(\dot m_s\) Steam flow kg/s
\(n\) Parallel tubes -
\(d_i\) Tube bore m
\(p\) Steam pressure (absolute) Pa
\(T\) Steam temperature K
\(\rho\) Steam density kg/m³
\(G\) Mass flux kg/(m²·s)
\(v\) Steam velocity m/s

Method and standards

Continuity: mass flux is the steam flow over the total bore area of the parallel tubes; velocity is the mass flux over the IAPWS-IF97 steam density at the pressure and temperature entered.

Where it is used

  • Superheater design checks.
  • Overheating investigations.

Common mistakes

  • Counting all tubes instead of parallel paths.

Assumptions and limits

  • Uniform distribution between the tubes; whole number of tubes.
  • One steam state: the density changes along a superheater, so enter the state where you want the velocity (the outlet, hottest steam, gives the highest velocity; the inlet the lowest).
  • Notes appear for zero flow and for a velocity outside 10–25 m/s.

References

  • Continuity G = ṁ/(n π d²/4); steam density from IAPWS-IF97

Questions and answers

Why mass flux?

It sets the steam-side heat-transfer coefficient that cools the tube.

Start-up?

With little steam flow the tubes are poorly cooled: limit firing until flow is established.

Velocity range?

Typically 10–25 m/s in superheaters; check with your design practice.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.