Steam Coil Air Preheater (SCAPH): Duty and Steam

Heat and steam to warm combustion air in a steam coil air preheater from the air flow and temperatures, with IF97 latent heat at the steam pressure.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolIAPWS-IF97 (water and steam)Economiser and air preheater

Inputs

Examples: 120 t/h air, 15 to 50 °CWinter, 5 to 60 °CSuperheated extraction steam at 4 bar(a), 200 °C

1006 J/(kg·K) is dry air near ambient; humid combustion air is 1–2 % higher. Use it with the air flow on the same (dry or humid) basis.
Absolute: add the atmospheric pressure to a gauge reading.

Results

A SCAPH raises the air heater's cold-end temperature at low load and in winter, at the cost of steam.

Air heating duty1,173.7kW
Latent heat at steam pressure2,133.3kJ/kg
Steam condensed1,872.6kg/h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 120 t/h air, 15 to 50 °C. The inputs, in the units selected above:

InputValue
Air flow120.00 t/h
Air in15.000 °C
Air out50.000 °C
Air specific heat1.0060 kJ/(kg·K)
Heating steam pressure (absolute)4.0000 bar
Heating steamDry saturated
Heating steam temperature (superheated only)200.00 °C

Applying the formula below gives:

ResultValue
Air heating duty1,173.7 kW
Latent heat at steam pressure2,133.3 kJ/kg
Steam condensed1,980.6 kg/h

Open this example in the calculator and change any input.

Formula

\(\dot Q = \dot m_a c_{p,a}(T_2 - T_1), \quad \dot m_s = \frac{\dot Q}{h_s - h_f(p_s)}, \quad h_{fg} = h_g - h_f\)

Variables

Symbol Meaning SI unit
\(\dot m_a\) Air flow kg/s
\(T_1\) Air in K
\(T_2\) Air out K
\(c_{p,a}\) Air specific heat J/(kg·K)
\(p_s\) Heating steam pressure (absolute) Pa
\(\dot Q\) Air heating duty W
\(h_{fg}\) Latent heat at steam pressure J/kg
\(\dot m_s\) Steam condensed kg/s
\(\text{state}\) Heating steam: dry saturated or superheated -
\(T_s\) Heating steam temperature (superheated only) K
\(h_s\), \(h_f\), \(h_g\) steam supplied, saturated liquid and saturated vapour enthalpies (IF97) J/kg

Method and standards

Energy balance: the air heating duty is supplied by steam condensing to saturated liquid at the steam pressure, so each kilogram gives h_s − h_f (the latent heat h_fg = h_g − h_f for dry saturated steam, more when superheated). IAPWS-IF97 properties.

Where it is used

  • SCAPH sizing.
  • Winter operation.

Common mistakes

  • Gauge pressure for latent heat.

Assumptions and limits

  • Saturated condensate out, no subcooling and no heat loss.
  • Heating steam dry saturated or superheated as chosen; wet steam gives less heat per kg and needs more steam than shown.
  • One air specific heat (default dry air near ambient); humid air is 1–2 % higher.
  • A note appears when the air leaves within 5 K of the steam temperature.

References

  • Energy balance with IAPWS-IF97 latent heat (saturated condensate)

Questions and answers

Why heat air with steam?

To keep the air heater cold end above the acid dew point when air is cold or load is low.

Is the steam wasted?

Partly recovered: hotter air reaches the furnace. The net cost is small compared with corrosion damage.

Which steam?

Low-pressure extraction or exhaust steam.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.