Worked example
Example: Indian coal 12 t/h, 25 % excess air, 180 to 130 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Carbon | 45.000 % |
| Hydrogen | 3.5000 % |
| Oxygen | 5.0000 % |
| Nitrogen | 1.0000 % |
| Sulphur | 0.50000 % |
| Ash | 35.000 % |
| Moisture | 10.000 % |
| Excess air | 25.000 % |
| Air humidity (kg water per kg dry air) | 0.013000 kg/kg |
| Fuel firing rate | 12,000 kg/h |
| Flue gas temperature now | 180.00 °C |
| Flue gas temperature after recovery | 130.00 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Heat available | 1,515.5 kW |
| Wet flue gas flow | 101,793 kg/h |
| Mean specific heat of the flue gas | 1.0720 kJ/(kg·K) |
Open this example in the calculator and change any input.
Formula
\(\dot Q = \dot m_f\,m_g\,\left[h_g(T_1) - h_g(T_2)\right] \qquad \dot m_g = \dot m_f\,m_g \qquad \bar c_p = \frac{h_g(T_1) - h_g(T_2)}{T_1 - T_2}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(C\), \(H\), \(O\), \(N\), \(S\), \(A\), \(M\) | ultimate analysis as fired, mass fractions | – |
| \(EA\) | excess air | – |
| \(\omega\) | air humidity, kg water per kg dry air | kg/kg |
| \(\dot m_f\) | fuel firing rate | kg/s |
| \(T_1\) | flue gas temperature now | K |
| \(T_2\) | flue gas temperature after recovery | K |
| \(\dot Q\) | heat available | W |
| \(\dot m_g\) | wet flue gas flow | kg/s |
| \(\bar c_p\) | mean specific heat of the flue gas | J/(kg·K) |
| \(m_g\) | wet flue gas per kg of fuel | kg/kg |
| \(h_g\) | enthalpy of the wet flue gas | J/kg |
Method and standards
Wet flue gas quantity and composition from FireCAD's exact-ratio combustion balance; enthalpy by integrating the NIST Shomate heat capacities of each gas.
Where it is used
- First screening of a waste heat recovery project before choosing the equipment.
- Sizing an economiser, air heater, thermic fluid heater or waste heat boiler duty.
- Furnaces, kilns, dryers and incinerators with a known fuel.
Common mistakes
- Counting heat below the acid dew point as recoverable for sulphur-bearing fuels.
- Using the stack temperature after dilution air or leakage.
- Forgetting that the receiving fluid needs a temperature difference: the gas cannot be cooled below the cold fluid's inlet temperature plus a pinch.
Assumptions and limits
- No condensation: water stays vapour. For cooling below the water dew point, use the condensing economiser calculator.
- Complete combustion; the sensible heat of fly ash and unburnt carbon carried in the gas is not included, which matters a little for high-ash fuels.
- A warning appears when \(T_2\) is below the water dew point (taken at atmospheric pressure) and, for sulphur-bearing fuels, a reminder about the acid dew point.
- The Shomate fits for water vapour are extended below their NIST lower limit (500 K); FireCAD checks the error there is under 1 %.
- In US units the heat is shown in Btu/h.
References
- NIST Chemistry WebBook Shomate equations
- ASME PTC 4-2013 (flue gas enthalpy)
Questions and answers
How much heat is in the flue gas?
Coal burned at 12 t/h with 25 % excess air makes 28.3 kg/s of wet flue gas; cooling it from 180 to 130 °C releases 1.52 MW. The mean specific heat over that range is 1.07 kJ/(kg·K).
Why not just use 1 kJ/(kg·K) for flue gas?
Flue gas is heavier in CO₂ and water vapour than air, so its specific heat is higher, and it rises with temperature. A fixed 1.0 underestimates the heat, typically by 5–20 %: the examples here give 1.07–1.18 kJ/(kg·K), the wettest fuels the most.
Can I use this for a furnace or kiln?
Yes, for any equipment burning a fuel of known analysis. For gas turbine or engine exhaust, use the gas properties calculator with the exhaust analysis.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.