FireCADCalc

Stack (Chimney) Diameter from Exit Velocity

Inside diameter of a stack or flue for a flue gas flow and design exit velocity, with the actual and normal gas volumes and the velocity in a chosen diameter.

Thermal power plantSugar mill and cogenerationChemical and fertiliserThermic fluid heatingPulp and paperBoilerStack and chimney

Inputs

Examples: Coal flue gas 60 t/h, 150 °C, 15 m/sGas-fired 20 t/h, 120 °C, 12 m/s, check 1.2 mUtility 900 t/h, 135 °C, 20 m/s, 0.98 bar

About 30 kg/kmol for coal and oil flue gas, 27.5–28.5 for natural gas.
The site barometric pressure.

Results

Required inside diameter4.2719m
Flow area14.333m²
Actual flue gas volume flow1,031,961m³/h
Normal flue gas volume flow (0 °C, 1 atm)667,966Nm³/h
Flue gas density at the exit0.87213kg/m³

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Coal flue gas 60 t/h, 150 °C, 15 m/s. The inputs, in the units selected above:

InputValue
Flue gas mass flow60,000 kg/h
Flue gas molar mass30.000 kg/kmol
Flue gas temperature at the exit150.00 °C
Pressure at the exit (absolute)1.0132 bar
Design exit velocity15.000 m/s
Chosen inside diameter to check (0 = skip)0 m

Applying the formula below gives:

ResultValue
Required inside diameter1.2796 m
Flow area1.2860 m²
Actual flue gas volume flow69,445 m³/h
Normal flue gas volume flow (0 °C, 1 atm)44,828 Nm³/h
Flue gas density at the exit0.86399 kg/m³

Open this example in the calculator and change any input.

Formula

\(\rho_g = \frac{p\,M_g}{R\,T_g} \qquad \dot V_g = \frac{\dot m_g}{\rho_g} \qquad A = \frac{\dot V_g}{v} \qquad D = \sqrt{\frac{4A}{\pi}}\)

\(\dot V_{g,N} = \frac{\dot m_g\,V_{m,N}}{M_g} \qquad v_{sel} = \frac{4\,\dot V_g}{\pi\,D_{sel}^2}\)

Variables

Symbol Meaning SI unit
\(\dot m_g\) flue gas mass flow kg/s
\(M_g\) flue gas molar mass kg/kmol
\(T_g\) flue gas temperature at the exit K
\(p\) absolute pressure at the exit Pa
\(v\) design exit velocity m/s
\(D_{sel}\) chosen inside diameter to check m
\(D\) required inside diameter m
\(A\) flow area m²
\(\dot V_g\) actual flue gas volume flow m³/s
\(\dot V_{g,N}\) normal flue gas volume flow (0 °C, 101.325 kPa) Nm³/s
\(\rho_g\) flue gas density at the exit kg/m³
\(v_{sel}\) exit velocity in the chosen diameter m/s
\(R\) universal gas constant J/(mol·K)
\(V_{m,N}\) molar volume at 0 °C, 101.325 kPa (22.414 m³/kmol) m³/kmol

Method and standards

Continuity for a circular duct and the ideal-gas density at the exit temperature and pressure. Normal volume with the ideal-gas molar volume at 0 °C and 101.325 kPa (CODATA 2018).

Where it is used

  • First sizing of chimneys and stacks.
  • Checking exit velocity for plume rise and downwash.
  • Retrofits that change gas flow.

Common mistakes

  • Using normal gas volume instead of actual at stack temperature.
  • Choosing a low exit velocity that causes downwash.
  • Ignoring part-load velocity.

Assumptions and limits

  • Circular inside section; for a rectangular flue use the equivalent diameter.
  • Uniform velocity over the section.
  • Ideal gas; the molar mass of wet flue gas is about 30 kg/kmol for coal and oil and 27.5–28.5 kg/kmol for natural gas.

References

  • Continuity equation; ideal gas (CODATA 2018 gas constant)

Questions and answers

How do I size a chimney diameter?

Divide the actual flue gas volume by the chosen exit velocity to get the area, then D = √(4A/π). 60 t/h of coal flue gas at 150 °C is 19.3 m³/s; at 15 m/s the stack needs a 1.28 m inside diameter.

Which exit velocity should I choose?

The calculator does not suggest one. The velocity comes from the plume-rise and downwash rules of your permit, the draught available and the fan design, so it is your input.

Why is the mass flow the input?

The mass flow is the same all along the gas path; the volume changes with temperature. The combustion air and flue gas calculator gives the flue gas mass flow and molar mass.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.