FireCADCalc

Hydropneumatic (Pressure) Tank Sizing

Drawdown volume and total size of a precharged pressure tank for a water pump from cut-in and cut-out pressures, precharge, pump flow and maximum starts per hour.

Inputs

Examples: Illustrative 60 L/min pumpSmall borewell 30 L/minBooster set 200 L/min

Accepted: 0.6 to 30,000 L/min
Accepted: 1 to 100
Accepted: 0 to 20 bar
Accepted: 0.1 to 30 bar
Accepted: 0 to 20 bar
Accepted: 0.5 to 1.1 bar

Results

The pump fills the tank between cut-in and cut-out; the air (or nitrogen behind a bladder) compresses by Boyle's law, so a tank of volume V precharged to p₀ holds V p₀(1/p₁ − 1/p₂) of usable water between the two pressures (absolute). Pump cycling is worst when demand is half the pump flow, giving a cycle time of 4V_d/Q, so V_d = Q/(4N) limits starts to N per hour. Set the precharge about 0.2 bar below the cut-in pressure.

Drawdown volume needed22.500L
Drawdown factor (share of tank volume)33.671%
Total tank volume66.822L
Minimum cycle time3.0000min

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 60 L/min pump. The inputs, in the units selected above:

InputValue
Pump flow60.000 L/min
Maximum pump starts per hour15.000 -
Cut-in pressure (gauge)2.0000 bar
Cut-out pressure (gauge)3.5000 bar
Precharge pressure (gauge, empty tank)1.8000 bar
Atmospheric pressure1.0132 bar

Applying the formula below gives:

ResultValue
Drawdown volume needed60.000 L
Drawdown factor (share of tank volume)31.030 %
Total tank volume193.36 L
Minimum cycle time4.0000 min

Open this example in the calculator and change any input.

Formula

\(V_d = \frac{\dot V}{4N}, \quad f_d = p_0\left(\frac{1}{p_{on}} - \frac{1}{p_{off}}\right), \quad V = \frac{V_d}{f_d}\)

Variables

Symbol Meaning SI unit
\(\dot V\) Pump flow m³/s
\(N\) Maximum pump starts per hour -
\(p_{on}\) Cut-in pressure (gauge) Pa
\(p_{off}\) Cut-out pressure (gauge) Pa
\(p_0\) Precharge pressure (gauge, empty tank) Pa
\(p_a\) Atmospheric pressure Pa
\(V_d\) Drawdown volume needed m³
\(f_d\) Drawdown factor (share of tank volume) -
\(V\) Total tank volume m³
\(t_c\) Minimum cycle time s

Method and standards

Pressure tank.

Where it is used

  • Booster sets, borewells and domestic water systems.
  • Reducing pump cycling.

Common mistakes

  • Using gauge instead of absolute pressures.
  • Precharging above the cut-in pressure.

Assumptions and limits

  • Isothermal gas; bladder tank.

References

  • Boyle's law drawdown and pump-cycling criterion

Questions and answers

How big a pressure tank does a 60 L/min pump need?

For 15 starts an hour and 2.0–3.5 bar, about 190 litres total (60 L drawdown).

Why does the tank hold so little water?

Only the air compression between cut-in and cut-out pressures pushes water out: typically a quarter to a third of the tank.

What do the defaults represent?

An illustrative 60 L/min pump with 2.0 bar cut-in, 3.5 bar cut-out, 1.8 bar precharge and at most 15 starts per hour.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.