Worked example
Example: Illustrative DN100, 50 m, 10 bar(a), 20 min. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Pipe mass per metre (with flanges) | 17.000 kg/m |
| Length between drain points | 50.000 m |
| Steam pressure (absolute) | 11.000 bar |
| Initial pipe temperature | 10.000 °C |
| Pipe specific heat | 0.49000 kJ/(kg·K) |
| Warm-up time | 20.000 min |
| Running heat loss per metre | 60.000 W/m |
| Trap safety factor | 2.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Steam saturation temperature | 184.07 °C |
| Latent heat | 1,999.5 kJ/kg |
| Warm-up condensate | 36.260 kg |
| Warm-up condensate rate | 108.78 kg/h |
| Running condensate rate | 5.4014 kg/h |
| Trap capacity needed | 217.56 kg/h |
Open this example in the calculator and change any input.
Formula
\(m_w = \frac{m'Lc(T_s - T_0)}{h_{fg}}, \quad \dot m_r = \frac{q'L}{h_{fg}}, \quad \dot m_{trap} = k_s\max(\dot m_w/t_w, \dot m_r)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(m'\) | Pipe mass per metre (with flanges) | kg/m |
| \(L\) | Length between drain points | m |
| \(p\) | Steam pressure (absolute) | Pa |
| \(T_0\) | Initial pipe temperature | K |
| \(c\) | Pipe specific heat | J/(kg·K) |
| \(t_w\) | Warm-up time | s |
| \(q'\) | Running heat loss per metre | W/m |
| \(k_s\) | Trap safety factor | - |
| \(T_s\) | Steam saturation temperature | K |
| \(h_{fg}\) | Latent heat | J/kg |
| \(m_w\) | Warm-up condensate | kg |
| \(\dot m_w\) | Warm-up condensate rate | kg/s |
| \(\dot m_r\) | Running condensate rate | kg/s |
| \(\dot m_{trap}\) | Trap capacity needed | kg/s |
Method and standards
Warm-up load.
Where it is used
- Steam main drain trap selection.
- Start-up procedures.
Common mistakes
- Sizing traps for running load only.
- Using full pressure for start-up trap capacity.
Assumptions and limits
- Uniform pipe; steel heated to saturation.
References
- Warm-up and running condensate loads
Questions and answers
Why is warm-up load larger than running load?
Heating tonnes of cold steel to steam temperature in minutes condenses far more steam than steady heat loss does.
Why drain every 30–50 m?
Condensate collecting in long mains causes water hammer; regular drain pockets with traps remove it.
What do the defaults represent?
An illustrative 50 m run of DN100 Sch 40 pipe (about 17 kg/m with flanges) warmed to 10 bar(a) steam from 10 °C in 20 minutes, 60 W/m running loss.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Spirax-Sarco, The Steam and Condensate Loop (Spirax-Sarco)