Worked example
Example: Illustrative 150 mm, 500 m at 1.5 m/s. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Pipe inside diameter | 150.00 mm |
| Pipe length | 500.00 m |
| Flushing velocity | 1.5000 m/s |
| Pipe volumes to flush | 3.0000 - |
| Water temperature | 20.000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Flushing flow | 95.426 m³/h |
| Reynolds number | 224,272 |
| Pipe volume | 8.8357 m³ |
| Total flushing water | 26.507 m³ |
| Flushing time | 16.667 min |
Open this example in the calculator and change any input.
Formula
\(Q = v\frac{\pi D^2}{4}, \quad V_t = nLA, \quad t = \frac{nL}{v}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(D\) | Pipe inside diameter | m |
| \(L\) | Pipe length | m |
| \(v\) | Flushing velocity | m/s |
| \(n\) | Pipe volumes to flush | - |
| \(T\) | Water temperature | K |
| \(Q\) | Flushing flow | m³/s |
| \(Re\) | Reynolds number | - |
| \(V_p\) | Pipe volume | m³ |
| \(V_t\) | Total flushing water | m³ |
| \(t\) | Flushing time | s |
Method and standards
Flushing.
Where it is used
- Commissioning of water, cooling and lube oil systems.
- Water main maintenance.
Common mistakes
- Flushing too slowly to lift debris.
- Ignoring disposal of the flushing water.
Assumptions and limits
- Full pipe; steady flow.
References
- Flushing flow and volume
Questions and answers
What velocity removes debris?
Sand and weld spatter move at about 1–1.5 m/s; heavier debris needs 2–3 m/s, which may require temporary pumps.
How many volumes?
Three to five pipe volumes, or until the outlet runs clear and samples pass.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Nayyar, Piping Handbook, 7th ed. (McGraw-Hill, 2000)