Worked example
Example: Illustrative 5 t/h fuel oil, 2 km. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Mass flow | 5.0000 t/h |
| Liquid specific heat | 2.0000 kJ/(kg·K) |
| Pipe outside diameter | 168.00 mm |
| Insulation thickness | 50.000 mm |
| Insulation conductivity | 0.045000 W/(m·K) |
| Outside heat transfer coefficient | 10.000 W/(m²·K) |
| Inlet temperature | 120.00 °C |
| Ambient temperature | 15.000 °C |
| Pipeline length | 2,000.0 m |
| Minimum allowed temperature | 80.000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Heat loss coefficient per metre | 0.56480 W/(m·K) |
| Outlet temperature | 84.917 °C |
| Heat lost | 97.454 kW |
| Length to reach the minimum temperature | 2.3586 km |
Open this example in the calculator and change any input.
Formula
\(T(x) = T_a + (T_0 - T_a)\exp\left(-\frac{U'x}{\dot mc_p}\right), \quad L_{min} = \frac{\dot mc_p}{U'}\ln\frac{T_0 - T_a}{T_{min} - T_a}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m\) | Mass flow | kg/s |
| \(c_p\) | Liquid specific heat | J/(kg·K) |
| \(D_o\) | Pipe outside diameter | m |
| \(t_{ins}\) | Insulation thickness | m |
| \(\lambda\) | Insulation conductivity | W/(m·K) |
| \(h_o\) | Outside heat transfer coefficient | W/(m²·K) |
| \(T_0\) | Inlet temperature | K |
| \(T_a\) | Ambient temperature | K |
| \(L\) | Pipeline length | m |
| \(T_{min}\) | Minimum allowed temperature | K |
| \(U'\) | Heat loss coefficient per metre | W/(m·K) |
| \(T_L\) | Outlet temperature | K |
| \(\dot Q\) | Heat lost | W |
| \(L_{min}\) | Length to reach the minimum temperature | m |
Method and standards
Line cooling.
Where it is used
- Fuel oil, bitumen and hot water lines.
- Deciding on tracing and insulation.
Common mistakes
- Checking only design flow, not turndown.
- Ignoring wet insulation.
Assumptions and limits
- Steady flow; constant properties; uniform insulation.
References
- Exponential temperature decay along an insulated pipe
Questions and answers
Why does temperature fall exponentially?
Heat loss is proportional to the remaining temperature difference, so each metre loses the same fraction of it.
How can I keep a line hotter?
Thicker insulation, higher flow, or heat tracing; low flow at turndown is often the critical case.
What do the defaults represent?
An illustrative 5 t/h of fuel oil (c_p 2 kJ/kg·K) entering a 6-inch line with 50 mm insulation at 120 °C, 2 km long, 15 °C ambient, not to drop below 80 °C.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Incropera and DeWitt, Fundamentals of Heat and Mass Transfer (Wiley)