Worked example
Example: Illustrative water 20 C, 200 mm steel, 10 K. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Liquid volumetric expansion coefficient | 2.0700e-04 1/K |
| Liquid compressibility | 0.45900 1/GPa |
| Pipe linear expansion coefficient | 1.2000e-05 1/K |
| Pipe mean diameter | 200.00 mm |
| Wall thickness | 8.0000 mm |
| Pipe elastic modulus | 200.00 GPa |
| Poisson's ratio | 0.30000 - |
| Temperature rise | 10.000 K |
Applying the formula below gives:
| Result | Value |
|---|---|
| Pipe pressure compliance | 0.11875 1/GPa |
| Pressure rise per kelvin of heating | 2.9598 bar |
| Pressure rise | 29.598 bar |
Open this example in the calculator and change any input.
Formula
\(\frac{dp}{dT} = \frac{\beta - 3\alpha}{\kappa + \frac{D}{Et}\left(\frac54 - \nu\right)}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\beta\) | Liquid volumetric expansion coefficient | 1/K |
| \(\kappa\) | Liquid compressibility | 1/Pa |
| \(\alpha\) | Pipe linear expansion coefficient | 1/K |
| \(D\) | Pipe mean diameter | m |
| \(t\) | Wall thickness | m |
| \(E\) | Pipe elastic modulus | Pa |
| \(\nu\) | Poisson's ratio | - |
| \(\Delta T\) | Temperature rise | K |
| \(C_p\) | Pipe pressure compliance | 1/Pa |
| \(dp/dT\) | Pressure rise per kelvin of heating | Pa |
| \(\Delta p\) | Pressure rise | Pa |
Method and standards
Trapped-liquid pressure.
Where it is used
- Thermal relief valve justification.
- Hydrotest pressure-temperature correction.
Common mistakes
- Using water β at the wrong temperature.
- Ignoring pipe compliance for thin pipes.
Assumptions and limits
- Closed, thin-walled, unrestrained pipe; elastic.
References
- Volume balance of a closed liquid-full thin cylinder
Questions and answers
Why does trapped liquid build so much pressure?
Liquids are nearly incompressible, so a small expansion that the pipe cannot accommodate raises pressure by tens of bar.
Why does hydrotest pressure drift with sunshine?
Warming of the test water raises pressure by this mechanism; cooling lowers it and can be mistaken for a leak.
What do the defaults represent?
Illustrative water at 20 °C (β 2.07 × 10⁻⁴ /K, κ 0.459 /GPa) in a 200 mm, 8 mm wall steel pipe warmed by 10 K.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.