FireCADCalc

Tank Draining Time through an Orifice

Time to drain a vertical cylindrical tank from one level to another through a bottom orifice or nozzle, by Torricelli's law with a discharge coefficient.

Process steam and utilitiesRefinery and petrochemicalChemical and fertiliserTank and drum

Inputs

Examples: 3 m tank, 4 m to empty, 50 mm sharp orifice1.5 m tank, 2.5 to 0.5 m, 25 mm stub10 m tank, 8 to 2 m, 150 mm nozzle

About 0.61 for a sharp-edged orifice; 0.8 for a short pipe stub; 0.95–0.98 for a rounded nozzle.

Results

Tank open to air (or vented) and discharging to air; outlet pipe friction and a vortex at low level would lengthen the time.

Draining time29.604min
Initial outflow9.8994m³/h
Volume drained3.5343m³

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 3 m tank, 4 m to empty, 50 mm sharp orifice. The inputs, in the units selected above:

InputValue
Tank inside diameter3.0000 m
Starting liquid level above the outlet4.0000 m
Final liquid level above the outlet0 m
Outlet orifice or nozzle diameter50.000 mm
Discharge coefficient61.000 %

Applying the formula below gives:

ResultValue
Draining time88.839 min
Initial outflow38.192 m³/h
Volume drained28.274 m³

Open this example in the calculator and change any input.

Formula

\(t = \frac{A_t}{C_d\,a}\sqrt{\frac{2}{g}}\left(\sqrt{h_1} - \sqrt{h_2}\right) \qquad Q_1 = C_d\,a\sqrt{2 g h_1} \qquad V = A_t (h_1 - h_2)\)

Variables

Symbol Meaning SI unit
\(D_t\) tank diameter m
\(h_1\) starting level m
\(h_2\) final level m
\(d\) outlet diameter m
\(C_d\) discharge coefficient –
\(t\) draining time s
\(Q_1\) initial outflow m³/s
\(V\) volume drained m³
\(A_t, a\) tank and outlet areas m²
\(g\) standard gravity m/s²

Method and standards

Torricelli's law integrated over the falling level of a constant-area tank.

Where it is used

  • Emergency draining of tanks.
  • Batch transfer times.
  • Fire water and storage tank checks.

Common mistakes

  • Using the level above the floor instead of above the outlet.
  • Cd of 1 for a sharp hole.
  • Closed tanks without a vent.

Assumptions and limits

  • The velocity of the falling liquid surface is neglected: the exact Torricelli result divides the outflow velocity by √(1 − (C_d a/A_t)²). The error is below 1 % while the outlet is under about 0.3 of the tank diameter; the page warns above that.

  • Vented tank; discharge to atmosphere; quasi-steady flow.

References

  • Torricelli's law with a discharge coefficient

Questions and answers

How long does a 3 m tank take to drain 4 m through a 50 mm orifice?

About 89 minutes with Cd 0.61; the first flow is 38 m³/h and it drains 28.3 m³.

Why does it slow down?

Outflow goes with the square root of the head, so the last metre takes longest.

Does outlet piping matter?

Yes; pipe friction lowers the flow. Use an effective Cd for the whole outlet.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.