Flow Split Between Two Parallel Pipes

Flow in each of two parallel pipe branches with the same pressure drop, from their lengths, diameters and roughness, by Colebrook friction factors.

Process steam and utilitiesRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: 100 m³/h: 200 m of DN100 and 300 m of DN80Equal branches 50 m of 50 mmViscous oil 5 m³/h: 30 m of 40 mm and 40 m of 50 mm (laminar)

Results

Straight pipe friction only; add fittings as equivalent length to each branch. Laminar flow uses 64/Re.

Flow in branch 11.6468m³/h
Flow in branch 23.3532m³/h
Common pressure drop39.964kPa
Share in branch 132.937%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 100 m³/h: 200 m of DN100 and 300 m of DN80. The inputs, in the units selected above:

InputValue
Total flow100.00 m³/h
Length of branch 1200.00 m
Diameter of branch 1102.30 mm
Length of branch 2300.00 m
Diameter of branch 277.900 mm
Pipe roughness0.045000 mm
Fluid density998.00 kg/m³
Dynamic viscosity0.001000 Pa·s

Applying the formula below gives:

ResultValue
Flow in branch 171.790 m³/h
Flow in branch 228.210 m³/h
Common pressure drop104.19 kPa
Share in branch 171.790 %

Open this example in the calculator and change any input.

Formula

\(\Delta p = f_1 \frac{L_1}{d_1}\frac{\rho v_1^2}{2} = f_2 \frac{L_2}{d_2}\frac{\rho v_2^2}{2}, \quad Q_1 + Q_2 = Q\)

Variables

Symbol Meaning SI unit
\(Q\) Total flow m³/s
\(L_1\) Length of branch 1 m
\(d_1\) Diameter of branch 1 m
\(L_2\) Length of branch 2 m
\(d_2\) Diameter of branch 2 m
\(\varepsilon\) Pipe roughness m
\(\rho\) Fluid density kg/m³
\(\mu\) Dynamic viscosity Pa·s
\(Q_1\) Flow in branch 1 m³/s
\(Q_2\) Flow in branch 2 m³/s
\(\Delta p\) Common pressure drop Pa
\(Q_1/Q\) Share in branch 1 -

Method and standards

Bisection on the split until the drops match.

Where it is used

  • Bypass lines and loops.
  • Cooling water distribution.

Common mistakes

  • Assuming equal split.
  • Ignoring fittings.

Assumptions and limits

  • Incompressible, steady flow.
  • The friction factor jumps from 64/Re to Colebrook at Re 2300; a branch between Re 2000 and 4000 gets a warning that the split is uncertain.

References

  • Darcy–Weisbach with Colebrook friction factor; equal pressure drop in parallel branches

Questions and answers

Why does the smaller branch get less than its area share?

Pressure drop rises roughly with v² and 1/d, so narrow pipes resist more per unit flow.

Must both branches have the same pressure drop?

Yes, they start and end at the same points.

What about valves in a branch?

Add their K as equivalent length to that branch.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.