FireCADCalc

Liquid Jet Trajectory: Reach and Height of a Nozzle or Monitor

Exit velocity of a liquid jet from nozzle pressure, and its trajectory without air drag: maximum height, horizontal reach, time of flight and the reach at 45°.

Thermal power plantRefinery and petrochemicalChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 7 bar at 30°, 1.5 m2 bar horizontal from 3 m

Results

Air drag and break-up shorten real reach a great deal: large fire-monitor jets reach roughly half to three-quarters of the no-drag value. Use makers' test data for firefighting design.

Jet exit velocity19.019m/s
Maximum height above the nozzle0m
Time of flight0.78220s
Horizontal reach to the target level14.877m
Reach at 45° from target level (no drag)36.886m

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 7 bar at 30°, 1.5 m. The inputs, in the units selected above:

InputValue
Pressure at the nozzle7.0000 bar
Liquid density998.00 kg/m³
Nozzle velocity coefficient0.97000 -
Elevation angle30.000 °
Nozzle height above the target level1.5000 m

Applying the formula below gives:

ResultValue
Jet exit velocity36.330 m/s
Maximum height above the nozzle16.824 m
Time of flight3.7855 s
Horizontal reach to the target level119.10 m
Reach at 45° from target level (no drag)134.59 m

Open this example in the calculator and change any input.

Formula

\(V_0 = C_v\sqrt{\frac{2\Delta p}{\rho}}, \quad t = \frac{V_0\sin\theta + \sqrt{V_0^2\sin^2\theta + 2gh_0}}{g}, \quad x = V_0\cos\theta\ t, \quad h_{max} = \frac{V_0^2\sin^2\theta}{2g}\)

Variables

Symbol Meaning SI unit
\(\Delta p\) Pressure at the nozzle Pa
\(\rho\) Liquid density kg/m³
\(C_v\) Nozzle velocity coefficient -
\(\theta\) Elevation angle rad
\(h_0\) Nozzle height above the target level m
\(V_0\) Jet exit velocity m/s
\(h_{max}\) Maximum height above the nozzle m
\(t\) Time of flight s
\(x\) Horizontal reach to the target level m
\(x_{45}\) Reach at 45° from target level (no drag) m

Method and standards

Bernoulli and projectile motion.

Where it is used

  • Cooling-tower and spray-pond nozzles.
  • Wash and fire-water monitors (first estimate).

Common mistakes

  • Ignoring drag for long throws.
  • Gauge vs. absolute pressure (use the gauge pressure across the nozzle).

Assumptions and limits

  • No air drag; jet stays coherent.

References

  • Bernoulli exit velocity and projectile motion without drag (definitions)

Questions and answers

Why does the real jet fall short?

Air drag and break-up into drops; the no-drag value is an upper bound.

Which angle throws farthest?

45° without drag; with drag the best angle is about 30–35°.

What do the defaults give?

7 bar at 30° from 1.5 m: about 36 m/s exit and over 100 m in theory, much less in practice.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.