Worked example
Example: Illustrative 90 kW compressor at 60 % demand. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Power at full load | 90.000 kW |
| Free air delivery at full load | 15.000 m³/min |
| Average air demand | 9.0000 m³/min |
| Unloaded power as a share of full-load power | 25.000 % |
| VSD specific power relative to the fixed-speed machine at full load | 1.0500 - |
| Running hours per year | 6,000.0 h |
| Electricity price per kWh (your currency) | 8.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Load factor | 60.000 % |
| Average power, load/unload | 63.000 kW |
| Specific power at this demand | 0.11667 kWh/m³ |
| Energy in a year, load/unload | 378.00 MWh |
| Average power with a VSD machine | 56.700 kW |
| Energy saved by a VSD in a year | 37.800 MWh |
| Cost saved in a year | 302,400 |
Open this example in the calculator and change any input.
Formula
\(\bar P = P_f\left[\frac{Q_d}{Q} + f_u\left(1 - \frac{Q_d}{Q}\right)\right], \quad P_v = k_v P_f \frac{Q_d}{Q}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P_f\) | Power at full load | W |
| \(Q\) | Free air delivery at full load | m³/s |
| \(Q_d\) | Average air demand | m³/s |
| \(f_u\) | Unloaded power as a share of full-load power | - |
| \(k_v\) | VSD specific power relative to the fixed-speed machine at full load | - |
| \(t\) | Running hours per year | s |
| \(c\) | Electricity price per kWh (your currency) | - |
| \(Q_d/Q\) | Load factor | - |
| \(\bar P\) | Average power, load/unload | W |
| \(SP\) | Specific power at this demand | J/m³ |
| \(E\) | Energy in a year, load/unload | J |
| \(P_v\) | Average power with a VSD machine | W |
| \(\Delta E\) | Energy saved by a VSD in a year | J |
| \(\Delta C\) | Cost saved in a year | - |
Method and standards
Load/unload.
Where it is used
- Compressed-air energy audits.
- Business case for a VSD compressor.
Common mistakes
- Taking unloaded power as zero.
- Assuming a VSD saves energy at full load.
Assumptions and limits
- Steady average demand; one compressor; no blow-down or cycling penalty.
References
- Load/unload averaging and proportional VSD power
- Bureau of Energy Efficiency
- Energy Efficiency in Electrical Utilities (Guide Book 3)
- ch. 3 Compressed air system
Questions and answers
How much power does an unloaded screw compressor use?
Typically 20–30 % of full-load power, more with a small receiver and frequent cycling.
When does a VSD compressor pay?
When demand varies and averages well below full capacity, typically 40–80 %.
What do the defaults represent?
An illustrative 90 kW, 15 m³/min compressor meeting 9 m³/min average demand for 6,000 h at 8 per kWh.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.