Worked example
Example: 10 m³/min at 1,500 m, 35 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Rated FAD (at rated intake) | 10.000 m³/min |
| Rated intake pressure | 101.33 kPa |
| Rated intake temperature | 20.000 °C |
| Site altitude | 1,500.0 m |
| Site intake temperature | 35.000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Site ambient pressure (ISA) | 84.556 kPa |
| Mass flow ratio | 79.388 % |
| Delivery at site, as a volume at the rated intake conditions (mass-based) | 7.9388 m³/min |
Open this example in the calculator and change any input.
Formula
\(p_s = p_0\left(1 - \frac{L z}{T_0}\right)^{g_0 M/(R^* L)}\ \text{(ISO 2533)}, \quad \frac{\dot m_s}{\dot m_r} = \frac{p_s}{p_r}\frac{T_r}{T_s}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V_r\) | Rated FAD (at rated intake) | m³/s |
| \(p_r\) | Rated intake pressure | Pa |
| \(T_r\) | Rated intake temperature | K |
| \(z\) | Site altitude | m |
| \(T_s\) | Site intake temperature | K |
| \(p_s\) | Site ambient pressure (ISA) | Pa |
| \(\dot m_s/\dot m_r\) | Mass flow ratio | - |
| \(\dot V_{FAD,ref}\) | Delivery at site, as a volume at the rated intake conditions (mass-based) | m³/s |
Method and standards
Density ratio.
Where it is used
- Compressor selection for hill sites.
- Hot-season capacity checks.
Common mistakes
- Comparing FAD at different reference conditions.
- Ignoring intake temperature in plant rooms.
Assumptions and limits
- Constant intake volume: the site FAD (volume at site intake) stays near the rated value; the output is the site mass flow expressed as a volume at the rated intake conditions.
- Site pressure from FireCAD's ISO 2533 troposphere (p₀ 101 325 Pa, T₀ 288.15 K, L 0.0065 K/m).
References
- ISA pressure–altitude relation (ISO 2533) and ideal-gas density (definitions)
Questions and answers
Why does altitude cut output?
Thinner air carries less mass per cubic metre drawn in; users need mass, not intake volume.
How much per 1,000 m?
About 11–12 % less mass flow, before temperature effects.
What do the defaults represent?
A 10 m³/min compressor at 1,500 m with 35 °C intake.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.