Compressor Intake Air Temperature: Energy Saving

Power saved by drawing compressor intake air from a cooler place, as compression work for the same mass flow is proportional to inlet temperature.

Inputs

Examples: Illustrative 110 kW, 40 C room to 30 C outsideHot plant room 48 C to 35 CSmall difference

Accepted: -20 to 70 °C
Accepted: -20 to 70 °C
Accepted: 1 to 10,000 kW
Accepted: 0 to 8,760 h
Accepted: 0 to 1,000

Results

For the same mass of air and pressure ratio, compression work is proportional to the absolute inlet temperature, so drawing air at T_c instead of T_h saves 1 − T_c/T_h of the power: about 1 % for every 3 K. Compressor rooms often run 10–15 K above outside; a duct from a shaded outside intake recovers it. The figure assumes the plant needs the same mass of air; a fixed-volume compressor delivers more mass with cooler air, which shows up as shorter loaded time.

Power saved as a share3.1934%
Power saved3.5127kW
Energy saved in a year21.076MWh
Cost saved in a year168,609

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 110 kW, 40 C room to 30 C outside. The inputs, in the units selected above:

InputValue
Present intake temperature (inside the compressor room)40.000 °C
Cooler intake temperature (outside air)30.000 °C
Compressor power at present110.00 kW
Running hours per year6,000.0 h
Electricity price per kWh (your currency)8.0000 -

Applying the formula below gives:

ResultValue
Power saved as a share3.1934 %
Power saved3.5127 kW
Energy saved in a year21.076 MWh
Cost saved in a year168,609

Open this example in the calculator and change any input.

Formula

\(\frac{\Delta P}{P} = 1 - \frac{T_c}{T_h}\)

Variables

Symbol Meaning SI unit
\(T_h\) Present intake temperature (inside the compressor room) K
\(T_c\) Cooler intake temperature (outside air) K
\(P\) Compressor power at present W
\(t\) Running hours per year s
\(c\) Electricity price per kWh (your currency) -
\(1 - T_c/T_h\) Power saved as a share -
\(\Delta P\) Power saved W
\(\Delta E\) Energy saved in a year J
\(\Delta C\) Cost saved in a year -

Method and standards

Intake temperature.

Where it is used

  • Compressed-air energy audits.
  • Compressor house ventilation design.

Common mistakes

  • Using °C instead of kelvin in the ratio.
  • Ducting intake from a sunny roof.

Assumptions and limits

  • Same mass flow and pressure ratio; ideal-gas compression.

References

  • Compression work proportional to absolute inlet temperature
  • Bureau of Energy Efficiency
  • Energy Efficiency in Electrical Utilities (Guide Book 3)
  • ch. 3 Compressed air system

Questions and answers

How much power does cooler intake air save?

About 1 % for every 3 K: 10 K cooler intake at 40 °C saves 3.2 %.

Is the old rule 1 % per 4 °C right?

It is close: the exact figure is 1 − T_c/T_h with absolute temperatures, slightly more than 1 % per 4 K at normal temperatures.

What do the defaults represent?

An illustrative 110 kW compressor drawing room air at 40 °C instead of outside air at 30 °C, 6,000 h at 8 per kWh.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.