Worked example
Example: 10-day sludge age. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Wastewater flow | 2,000.0 m³/d |
| Influent BOD₅ | 300.00 mg/L |
| Effluent soluble BOD₅ | 10.000 mg/L |
| Yield (kg VSS per kg BOD₅) | 0.60000 - |
| Endogenous decay coefficient | 0.060000 1/d |
| Sludge age (SRT) | 10.000 d |
| Volatile share of the solids | 80.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Observed yield | 0.37500 |
| Biomass produced (VSS) | 217.50 kg/d |
| Total solids produced | 271.87 kg/d |
Open this example in the calculator and change any input.
Formula
\(Y_{obs} = \frac{Y}{1 + k_d\theta_c}, \quad P_x = Y_{obs}\,Q(S_0 - S)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | Wastewater flow | m³/s |
| \(S_0\) | Influent BOD₅ | kg/m³ |
| \(S\) | Effluent soluble BOD₅ | kg/m³ |
| \(Y\) | Yield (kg VSS per kg BOD₅) | - |
| \(k_d\) | Endogenous decay coefficient | 1/s |
| \(\theta_c\) | Sludge age (SRT) | s |
| \(VSS/TSS\) | Volatile share of the solids | - |
| \(Y_{obs}\) | Observed yield | - |
| \(P_x\) | Biomass produced (VSS) | kg/s |
| \(P_{TSS}\) | Total solids produced | kg/s |
Method and standards
Biomass balance.
Where it is used
- ETP sludge handling design.
- Dewatering equipment sizing.
Common mistakes
- Units of k_d.
- Total BOD for soluble.
Assumptions and limits
- Steady state, complete mix.
- The yield Y is on a BOD₅ basis (kg VSS per kg BOD₅ removed); yields quoted per kg bCOD are lower and must not be mixed in.
- Active biomass only: the cell-debris (endogenous residue) term and inert influent VSS are not included, so P_x is lower than a full Metcalf & Eddy VSS production.
- If the effluent BOD exceeds the influent, the removal is taken as zero and the page warns.
References
- P_x = Y Q (S₀ − S)/(1 + k_d θ_c) (Metcalf & Eddy)
Questions and answers
2000 m³/d, 290 mg/L removed, Y 0.6, k_d 0.06/d, SRT 10 d?
Observed yield 0.375: about 217 kg VSS a day.
Longer sludge age?
More decay: less sludge but more oxygen.
Industrial effluent?
Yields vary widely; measure if you can.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.